FieldServer FS-8700-20 Appendix A.2. DataType, Address & Length, DPBuffer Description

Page 16

FS-8700-20 Profibus DP Driver Manual

Page 16 of 22

Appendix A. Special Driver Parameters

Appendix A.1. DP_Buffer

Within the Profibus DP card, the FieldServer can access data from two distinct buffers. The Input buffer is the data that is sent from the slave to master. The Output buffer is the data sent from the master to the slave. Each Map Descriptor specifies which one of these buffers to access in the card.

DP_Buffer

Description

Input

Data to the master from a slave

Output

Data from the master to a slave

Appendix A.2. Data_Type, Address & Length

Each Map Descriptor also specifies the Profibus DP data type. The data arrives from a Slave or is sent from a Master as a sequence of bytes. By specifying the DP data type, the driver knows how to interpret the bytes within the buffer. The supported types are Bit, Byte, Word and Float. To indicate where in the buffer to access the data, the Address field is used. For Byte, Word and Float type mappings, the address specifies the offset in bytes from the beginning of the buffer. For Bit type mappings, the address specifies the offset in bits from the beginning of the buffer. A bit offset of 0 would access the least significant bit in the first byte in the designated buffer.

Data_Type

Description

Bit

Transfer Length bits to Data Array

Byte

Transfer Length bytes to Data Array

Word

Swap the bytes and transfer Length words to Data Array

Float

Swap the bytes and transfer Length floats to Data Array

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 16
Contents FS-8700-20 Profibus DP Table of Contents Profibus DP Description FS-8700-20 Profibus DP Driver ManualSoftware Provided by the Supplier of 3rd Party Equipment HardwareFieldServer Technologies Description Hardware Connections Hardware TroubleshootingSST Profibus card LEDs Profibus Master Configuration Using COM Profibus for Profibus Master ConfigurationGeneral Configuring the FieldServer as a Profibus DP MasterData Arrays/ Descriptors Client Side Connection Descriptions Client Side Node DescriptorsClient Side Map Descriptors RDBC, WrbcCreating the Network Configuration File for the Master Important Note FS-8700-20 Profibus DP Driver Manual Configuring the FieldServer as a Profibus DP Slave Only Server Side Connection Descriptions Server Side Node DescriptorsServer Side Map Descriptors DPBuffer Description Appendix A.2. DataType, Address & LengthDataType Description DPBuffer Function DP slave the data will be sent or fetched from FS-8700-20 Profibus DP Driver Manual Appendix C.2. FieldServer as a Profibus Master Master Mode not enabled This page Intentionally Left Blank