1.Profibus DP Description

The Profibus DP driver allows the FieldServer to transfer data to and from devices using Profibus DP protocol. The Communications Adapter card is included with the FieldServer. The FieldServer can function as either a Master or a Slave on the Profibus Network.

When acting as a DP Master, the FieldServer requires a Profibus master configuration file in

addition to its own configuration file. The Profibus master configuration file (bridge.bss/bridge.2bf) describes the operating network, and the FieldServer configuration file (config.csv) describes the data that will be accessed within the Profibus slaves. As slaves are added or removed from the Profibus network, the Profibus master configuration file will need to be updated. The Profibus master configuration is created using a Profibus configuration tool. The tool provided on the SST CD can be used to create this file.

As a slave, the Profibus DP driver allows the FieldServer to be a single slave station to another master. This slave is capable of transferring 244 bytes of input and 244 bytes of output to the other master. If it is necessary to transfer more data to a Profibus master, then the Profibus DPMS driver and adapter card will be necessary. For Slave applications, the Profibus master configuration file is not used, and only the FieldServer configuration file will be used to set the FieldServer’s Profibus Slave station address and buffer sizes.

To connect to the Profibus network, the FieldServer has been equipped with a 5136-PFB-ISA card. This card has a standard DB-9 Profibus port that will accommodate a DB9 (Male) Profibus connector (supplied) and drop cable (not supplied).

The 5136-PFB-ISA card requires firmware (PFBDP.SS1) which will be factory installed onto the FieldServer prior to shipment.

The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 3
Contents FS-8700-20 Profibus DP Table of Contents FS-8700-20 Profibus DP Driver Manual Profibus DP DescriptionProvided by the Supplier of 3rd Party Equipment Hardware SoftwareFieldServer Technologies Description Hardware Troubleshooting Hardware ConnectionsSST Profibus card LEDs Using COM Profibus for Profibus Master Configuration Profibus Master ConfigurationConfiguring the FieldServer as a Profibus DP Master GeneralData Arrays/ Descriptors Client Side Node Descriptors Client Side Connection DescriptionsRDBC, Wrbc Client Side Map DescriptorsCreating the Network Configuration File for the Master Important Note FS-8700-20 Profibus DP Driver Manual Configuring the FieldServer as a Profibus DP Slave Only Server Side Node Descriptors Server Side Connection DescriptionsServer Side Map Descriptors Appendix A.2. DataType, Address & Length DPBuffer DescriptionDataType Description DPBuffer Function DP slave the data will be sent or fetched from FS-8700-20 Profibus DP Driver Manual Appendix C.2. FieldServer as a Profibus Master Master Mode not enabled This page Intentionally Left Blank