FieldServer FS-8700-20 Configuring the FieldServer as a Profibus DP Master, General

Page 7

FS-8700-20 Profibus DP Driver Manual

Page 7 of 22

4.Configuring the FieldServer as a Profibus DP Master

The sections below describe the parameters available for configuring the driver as a Client. Note that * indicates an optional parameter, with the bold legal value being the default.

4.1.

General

 

 

 

 

 

 

 

Section Title

 

 

 

FieldServer

 

 

 

Column Title

Function

Legal Values

 

 

 

Provide a title for the

Up to 15 alphanumeric

 

Title

 

configuration file (displays on

 

 

characters

 

 

 

RUI editor)

 

 

 

 

 

 

 

 

 

System_Station_Address

Profibus DP Master Station ID

0-125

 

 

 

of the FieldServer

 

 

Example:

 

 

 

 

 

 

 

// Common information

 

 

 

FieldServer

 

 

 

Title,

 

System_Station_Address

 

Profibus DP Master,

0

 

4.2.Data Arrays/ Descriptors

Data Arrays are the neutral data buffers used by the FieldServer to pass data between communications drivers, and are defined as follows:

 

Section Title

 

 

 

 

Data_Arrays

 

 

 

 

Column Title

Function

 

Legal Values

 

Data_Array_Name

Provide name for Data Array

 

Up to 15 alphanumeric

 

 

characters

 

 

 

 

 

 

 

 

FLOAT, BIT, UInt16,

 

Data_Format

Provides data format

 

SInt16, Packed_Bit,

 

 

Byte, Packed_Byte,

 

 

 

 

 

 

 

 

Swapped_Byte

 

Data_Array_Length

Number of Data Objects

 

1-10,000

 

Example

 

 

 

 

 

 

 

 

 

// Data Arrays

 

 

 

 

Data_Arrays

 

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

 

DA_AI_01,

UInt16,

200

 

 

DA_AO_01,

UInt16,

200

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 7
Contents FS-8700-20 Profibus DP Table of Contents FS-8700-20 Profibus DP Driver Manual Profibus DP DescriptionSoftware Provided by the Supplier of 3rd Party Equipment HardwareFieldServer Technologies Description Hardware Connections Hardware TroubleshootingSST Profibus card LEDs Using COM Profibus for Profibus Master Configuration Profibus Master ConfigurationGeneral Configuring the FieldServer as a Profibus DP MasterData Arrays/ Descriptors Client Side Node Descriptors Client Side Connection DescriptionsRDBC, Wrbc Client Side Map DescriptorsCreating the Network Configuration File for the Master Important Note FS-8700-20 Profibus DP Driver Manual Configuring the FieldServer as a Profibus DP Slave Only Server Side Node Descriptors Server Side Connection DescriptionsServer Side Map Descriptors DPBuffer Description Appendix A.2. DataType, Address & LengthDataType Description DPBuffer Function DP slave the data will be sent or fetched from FS-8700-20 Profibus DP Driver Manual Appendix C.2. FieldServer as a Profibus Master Master Mode not enabled This page Intentionally Left Blank