FieldServer FS-8700-20 instruction manual DPBuffer Function

Page 17

FS-8700-20 Profibus DP Driver Manual

Page 17 of 22

Appendix B. Driver Notes

Appendix B.1. Understanding buffer types and Map Descriptor functions

The following DP_Buffer types and Map Descriptor functions are normally used together when the FieldServer is used as a DP Master:

DP Master:

DP_Buffer

Function

Output

WRBC

Input

RDBC

The Buffer functions are reversed when using the FieldServer as a DP Slave:

DP Slave:

DP_Buffer

Function

Output

RDBC

Input

WRBC

The diagram below explains the data flows for both buffers when using the FieldServer as a DP Master:

Note that for the Input buffer, the data is coming from the external DP Slave and is transferred into the DP Master card’s internal input buffer. The Map Descriptor being of the RDBC function ( Read Data Block Continuous ) transfers the data from the card buffer into the FieldServer’s Data Array packing it correctly according to the specified DP_Type.

For the Output buffer, the data is written from the FieldServer’s Data Array by the WRBC function Map Descriptor ( Write Data Block Continuous ) into the DP Master card’s internal output buffer from where it is transferred across the Profibus network to the external DP Slave’s input buffer.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 17
Contents FS-8700-20 Profibus DP Table of Contents FS-8700-20 Profibus DP Driver Manual Profibus DP DescriptionFieldServer Technologies Description Provided by the Supplier of 3rd Party Equipment HardwareSoftware SST Profibus card LEDs Hardware TroubleshootingHardware Connections Using COM Profibus for Profibus Master Configuration Profibus Master ConfigurationData Arrays/ Descriptors Configuring the FieldServer as a Profibus DP MasterGeneral Client Side Node Descriptors Client Side Connection DescriptionsRDBC, Wrbc Client Side Map DescriptorsCreating the Network Configuration File for the Master Important Note FS-8700-20 Profibus DP Driver Manual Configuring the FieldServer as a Profibus DP Slave Only Server Side Node Descriptors Server Side Connection DescriptionsServer Side Map Descriptors DataType Description Appendix A.2. DataType, Address & LengthDPBuffer Description DPBuffer Function DP slave the data will be sent or fetched from FS-8700-20 Profibus DP Driver Manual Appendix C.2. FieldServer as a Profibus Master Master Mode not enabled This page Intentionally Left Blank