FS-8704-16 Omron FINS Manual

Page 5 of 37

The switches are all factory-set to 0 (00.00.00.00). The Ethernet Unit cannot be used with this setting; a proper IP address must be set.

The following settings cannot be made for the IP address, or the ERC indicator will flash. All bits in the network number field set to 0 or 1.

All bits in the host number field set to 0 or 1. All bits in the subnet number field set to 1.

The beginning of the IP address set to 127 (7F Hex) Example: 127.35.21.16

Note 1. When using the automatic generation method for address conversion, set switches 7 and 8 to the same values as the node number setting, and set the rest of the host number to zeroes. For details regarding the host number, refer to 1-7 IP Addresses. The value for the host number field in the IP address must match the value for the node number or the ERC indicator will flash.

2.If a subnet mask is to be set, use the CX-Programmer to set it in the CPU Bus Unit System Setup. For details, refer to 4-2 CPU Bus Unit System Setup.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 8
Contents FS-8704-16 Omron Fins Effective for all systems manufactured after May 1Table of Contents Appendix D Revision History Appendix C Troubleshooting tipsAppendix B Driver Notes Max Nodes Supported FieldServer Mode Comments FS-8704-16 Omron Fins Manual Omron Fins DescriptionRequired 3rd Party Configuration FS-8704-16 Omron Fins Manual Driver Scope of SupplyFieldServer Technologies Description Required 3rd Party HardwareFS-8704-16 Omron Fins Manual Hardware Connections FS-8704-16 Omron Fins Manual Setting the Node NumberSetting the Local IP Address FS-8704-16 Omron Fins Manual Section Title Column Title Function Legal ValuesFS-8704-16 Omron Fins Manual Example PLC Driver Related Map Descriptor Parameters WordUnitNumber Unit number of CPU at Cmdcio Dacio Rdbc PLC1 CIO-WORD Memory Area Read MRC -SRC Map Descriptor Example 4 Clock Write Map Descriptor Example 5 Read CPU Cycle TimesMap Descriptor Example 7 Read CPU Status 010 Server Side Connection Descriptors 011 Server Side Node Descriptors CIO-WORD, WR-WORD Data Array Map Descriptor Example 5 CPU Cycle Times Map Descriptor Example 7 CPU Status FS-8704-16 Omron Fins Manual Appendix A. Advanced Topics DIP UM Appendix A.3 End Codes FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual Clock Information Element Contents CPU Cycle Time Element ContentsPLC Mode Stored Value FS-8704-16 Omron Fins Manual Appendix B. Driver NotesElement Contents Description Number Stat Stats Description Number Error Message Description and Action Required FinsnowrthuPage Appendix C.1. Connection Tips & Hints FS-8704-16 Omron Fins Manual Comment Ver Rev PMC