FieldServer instruction manual FS-8704-16 Omron Fins Manual

Page 39

FS-8704-16 Omron FINS Manual

Page 36 of 37

Therefore the PLC responds to 192.168.0.34 which is clearly the wrong address and the FieldServer will not see the response.

Example: - Class A Addressing

A FieldServer with IP address=192.168.1.81 and system_node_id=34 polls for data from a PLC with IP address =192.168.2.33 and Subnet mask = 255.255.0.0

The PLC responds to

192.168.2.33

255.0.0.0

192.x.x.y

Where x is always set to zero and

y is equal to 34 (The PLC obtains the node ID of 34 by inspecting the contents of the poll message.)

Therefore the PLC responds to 192.0.0.34 which is clearly the wrong address and the FieldServer will not see the response.

Thus, if the PLC is using Class A/B IP addressing then the 3rd (Class B) or the 2nd and 3rd (Class A) bytes of the address must be zero as must the FieldServer's if communications are to work.

There are ways around this problem, we believe. The solution requires usage of the Omron PLC routing table. For more help consult with Omron's Tech Support.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 39
Contents Effective for all systems manufactured after May 1 FS-8704-16 Omron FinsTable of Contents Appendix C Troubleshooting tips Appendix B Driver NotesAppendix D Revision History FS-8704-16 Omron Fins Manual Omron Fins Description Max Nodes Supported FieldServer Mode CommentsRequired 3rd Party Hardware Required 3rd Party ConfigurationFS-8704-16 Omron Fins Manual Driver Scope of Supply FieldServer Technologies DescriptionFS-8704-16 Omron Fins Manual Hardware Connections Setting the Node Number Setting the Local IP AddressFS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual Column Title Function Legal Values Section TitleFS-8704-16 Omron Fins Manual Example PLC Word Driver Related Map Descriptor ParametersUnitNumber Unit number of CPU at Cmdcio Dacio Rdbc PLC1 CIO-WORD Memory Area Read MRC -SRC Map Descriptor Example 5 Read CPU Cycle Times Map Descriptor Example 4 Clock WriteMap Descriptor Example 7 Read CPU Status 010 Server Side Connection Descriptors 011 Server Side Node Descriptors CIO-WORD, WR-WORD Data Array Map Descriptor Example 5 CPU Cycle Times Map Descriptor Example 7 CPU Status FS-8704-16 Omron Fins Manual Appendix A. Advanced Topics DIP UM Appendix A.3 End Codes FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual Appendix B. Driver Notes Clock Information Element ContentsCPU Cycle Time Element Contents PLC Mode Stored ValueElement Contents Description Number Stat Stats Description Number Finsnowrthu Error Message Description and Action RequiredPage Appendix C.1. Connection Tips & Hints FS-8704-16 Omron Fins Manual PMC Comment Ver Rev