Page 15 of 37 |
5.Configuring the FieldServer as a FINS Server
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver CD).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a FINS Client.
As a Server, the Driver responses to read requests and updates the FieldServer Data Arrays with write requests from the Client.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for FINS communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
1.010 | Server Side Connection Descriptors |
| ||
|
|
|
|
|
|
| Section Title |
|
|
| Adapter |
|
| |
|
| Column Title | Function | Legal Values |
| Adapter | Adapter Name | N1, N24 | |
| Protocol | Specify protocol used | Fins, omn_fins or fins_udp | |
| Udp_port_number | Specify UDP port number | 0,9600 etc | |
| Example |
|
| |
|
|
|
|
|
| // | Server Side |
|
|
| Connections |
|
| |
| Adapters |
|
| |
| Adapter, | Protocol, | Udp_port_number | |
| N1, | Fins, | 9600 |
4Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408)