FieldServer FS-8704-16 instruction manual Section Title, Column Title Function Legal Values

Page 9

FS-8704-16 Omron FINS Manual

Page 6 of 37

4.Configuring the FieldServer as a FINS Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a FINS Server. As a Client this driver reads and writes data to Server Nodes. Server nodes should be FINS capable and be configured to communicate over FINS

1.05Data Arrays/Descriptors

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for FINS communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

 

Section Title

 

 

 

Data_Arrays

 

 

 

Column Title

Function

Legal Values

 

Data_Array_Name

Provide name for Data Array

Up to 15 alphanumeric

 

characters

 

 

 

 

 

Provide data format. Each Data

Float, Bit, UInt16,

 

 

SInt16, Packed_Bit,

 

Data_Array_Format

Array can only take on one

 

Byte, Packed_Byte,

 

 

format.

 

 

Swapped_Byte

 

 

 

 

 

Number of Data Objects. Must

 

 

 

be larger than the data storage

 

 

Data_Array_Length

area required by the Map

1-32767

 

 

Descriptors for the data being

 

 

 

placed in this array.

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 9
Contents Effective for all systems manufactured after May 1 FS-8704-16 Omron FinsTable of Contents Appendix C Troubleshooting tips Appendix B Driver NotesAppendix D Revision History FS-8704-16 Omron Fins Manual Omron Fins Description Max Nodes Supported FieldServer Mode CommentsFS-8704-16 Omron Fins Manual Driver Scope of Supply Required 3rd Party ConfigurationFieldServer Technologies Description Required 3rd Party HardwareFS-8704-16 Omron Fins Manual Hardware Connections Setting the Node Number Setting the Local IP AddressFS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual Column Title Function Legal Values Section TitleFS-8704-16 Omron Fins Manual Example PLC Word Driver Related Map Descriptor ParametersUnitNumber Unit number of CPU at Cmdcio Dacio Rdbc PLC1 CIO-WORD Memory Area Read MRC -SRC Map Descriptor Example 5 Read CPU Cycle Times Map Descriptor Example 4 Clock WriteMap Descriptor Example 7 Read CPU Status 010 Server Side Connection Descriptors 011 Server Side Node Descriptors CIO-WORD, WR-WORD Data Array Map Descriptor Example 5 CPU Cycle Times Map Descriptor Example 7 CPU Status FS-8704-16 Omron Fins Manual Appendix A. Advanced Topics DIP UM Appendix A.3 End Codes FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual FS-8704-16 Omron Fins Manual CPU Cycle Time Element Contents Clock Information Element ContentsPLC Mode Stored Value FS-8704-16 Omron Fins Manual Appendix B. Driver NotesElement Contents Description Number Stat Stats Description Number Finsnowrthu Error Message Description and Action RequiredPage Appendix C.1. Connection Tips & Hints FS-8704-16 Omron Fins Manual PMC Comment Ver Rev