FieldServer FS-8700-31 instruction manual C18FLOATPLC254

Page 14

FS-8700-31 Siemens TIWAY I

Page 11 of 23

The above map descriptor will continuously write data of type “Loop_Gain” to 2 PLC data memory addresses of 5 and 9. The data to write will be collected from the data array “FLOAT_Data” from offsets 0 and 1.

4.4.5.3.Writing the same value to a block of contiguous PLC data memory locations

Map_Descriptor_Name,

Data_Array_Name, Data_Array_Offset,

Function,

Node_name,

TIWAY_Data_Type,

Address,

Length,

C18_FLOAT_PLC254,

FLOAT_Data,

10,

WRBC,

PLC_254,

Loop_Reset,

0,

3,

TIWAY_Fill_Block_Value, Scan_Interval

 

 

 

 

 

 

50.5,

0s

 

 

 

 

 

 

The above map descriptor will continuously write a value of 50.5 of type “Loop_Reset” to 3 contiguous PLC data memory addresses starting from 0.

4.4.5.4.Writing Drum_Count_Preset data to contiguous PLC data memory locations

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

TIWAY_Data_Type, Address,

Length,

C08_RAW16_PLC01,

RAW16_Data,

70,

WRBC,

PLC_01,

Drum_Count_Preset, 0,

5,

Preset_Step_List,

Scan_Interval

 

 

 

 

 

5 8 9 33 49,

0s

 

 

 

 

 

 

The above map descriptor will continuously write data of type “Drum_Count_Preset” to 5 PLC data memory addresses. The data to write will be collected from the data array “RAW16_Data” from an offset of 70. The Preset Steps associated with the addresses are (address 0):5, (address 1):8, (address 2):9, (address 3):33, and (address 4):49.

4.4.5.5.Writing Drum_Count_Preset data to random PLC data memory locations

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

TIWAY_Data_Type, TIWAY_Address_List,

C08_RAW16_PLC01,

RAW16_Data,

70,

WRBC,

PLC_01,

Drum_Count_Preset, 5 9,

Length, Preset_Step_List, Scan_Interval

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 14
Contents FS-8700-31 Siemens Tiway Effective for all systems manufactured after May 1Table of Contents Advanced Topics Driver Notes Troubleshooting tips FS-8700-31 Siemens Tiway IPage 1 FieldServer Mode Nodes CommentsSiemens Tiway I Driver Description Required 3rd Party Software Required 3rd Party ConfigurationProvided by the Supplier of 3rd Party Equipment Hardware Optional ItemsHardware Connection Tips / Hints Configuring the FieldServer as a Tiway ClientHardware Connections Data Arrays/DescriptorsColumn Title Function Legal Values Client Side Connection DescriptionsSection Title ExampleClient Side Node Descriptors FS-8700-31 Siemens Tiway ExampleBit byte datatypes Driver Related Map Descriptor ParametersBit word datatypes Bit float datatypesPacked-bit datatypes Timing ParametersBit datatypes Reading data from random PLC data memory locations Reading secondary PLC status Writing data to random PLC data memory locations C18FLOATPLC254 Read Secondary Log Tiway host adapter command map descriptor examplesReport HIU Configuration Report Adapter Configuration Report Network Manager ConfigurationSoft Reset Forces the Unilink Host Adapter to do a software resetConnect Secondaries Reset AdapterDisconnect Secondaries FS-8700-31 Siemens Tiway FS-8700-931 Siemens Tiway Configuring the FieldServer as a Tiway ServerServer Side Connection Descriptors Server Side Node Descriptors FS-8700-931 Siemens Tiway ExampleDriver Specific Map Descriptor Parameters Bit float datatypes Serving PLC status data map descriptor example Serving DrumCountPreset Tiway data map descriptor exampleServing Tiway data map descriptor example Driver Notes Troubleshooting tips Connection Tips & HintsAdvanced Topics FS-8700-31 Siemens Tiway IPage 23 Date Driver Document Resp Comment Version Revision