FieldServer FS-RA-CLX-BAS instruction manual Inside Cover Door Label, Technical Specifications

Page 9

FS-RA-CLX_SlotServer_Instruction_Manual_(T17011)

Page 9 of 34

TP/FT10 LonWorks connection

This two wire connection is polarity insensitive and can be multi-dropped into a LonWorks Network.

Ethernet Port

The Ethernet port can be used for configuration and troubleshooting, as well as for Protocols that require an Ethernet connection. Use standard Ethernet cables for this connection.

RS-485 Port

This is a standard 2-wire RS-485 port. Specify as R1 in the configuration.

4.2.Inside Cover Door Label

A label has been provided on the inside of the cover door for the User to document important or useful configuration parameters used. In particular, special provision has been made to document the Ethernet port IP parameters, as well as the LonWorks DSN (Domain/Subnet/Node) allocated by the Network Manager. These fields are there to be utilized at the User’s discretion.

4.3.Technical Specifications

Slot width

1

BackPlane Current Load

0.6A

Operating Temperature

0-60 Deg C (32-140 Deg F)

Storage Temperature

-40 – 85 Deg C (-40 – 185 Deg F)

Humidity

5-95% (Non-Condensing)

Allen Bradley Platform:

ControlLogix 1756 Rack

LonWorks Connection type:

TP/FT-10

Ethernet port

10/100 MB/sec.

RS-485 port

2-wire, half duplex.

Approvals1

UL 60950-1:2003

 

CAN/CSA-C22.2 No.60950-1-03

1Refer to Error! Reference source not found. to view Certificates.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 9
Contents Applicability & Effectivity Table of Contents Appendix B Troubleshooting Tips Introduction About this product Rslogix Required configuration for the SlotServer Write the SlotServer configuration Install the SlotServer in a ControlLogix Rack Install the FieldServer Utilities Load the SlotServer Configuration into the SlotServerSlotServer Ports and Displays SlotServer InstallationLED Inside Cover Door Label Technical SpecificationsSlotServer Topology Data Arrays/Descriptors Configuring the SlotServer as a Logix I/O ServerServer Side Node Descriptors Server Side Connection DescriptorsDriver Specific Map Descriptor Parameters Map Descriptors Example Establish an RSLogix project5 Add and configure the SlotServer as an IO Module Write Ladder Program to get Input Data from Data Arrays FS-RA-CLXSlotServerInstructionManualT17011 Very Important Note Set up the third party connection Write Ladder Program to Send Output Data to Data ArraysDownload the RSLogix Program and Run Multiple Input Data Arrays Accessing Multiple Output Data ArraysVery Important Note FS-RA-CLXSlotServerInstructionManualT17011 SlotServer Data Transfer over IO Data Image Appendix A.2. The IO image header Appendix A.3. How to obtain Node Status from the SlotServerAppendix A.4. Dealing with ControlLogix RPI Settings Appendix A.5.3. RSLogix configuration Appendix A.5.2. SetupAppendix A.5.4. RSNetWorx configuration Appendix A.5.5. Testing FS-RA-CLXSlotServerInstructionManualT17011 Appendix A.6. Rules for Naming Logix driver Data Arrays Rdbc CPU1 INT Wrbc CPU1 INTFS-RA-CLXSlotServerInstructionManualT17011 This page Intentionally Left Blank