Installation 2
Power Wiring:
Power connections are made at the 2 position terminal block located on the module board marked +5V and GND No. 8 captive wire clamps accept
Power wiring conventions:
+of the power source to the terminal marked +5V
-of the power source to the terminal marked GND
Power requirements
Voltage: | 5.0- 5.4Vdc |
Current: | 250 mA + 25mA per digital module and 200mA per analog module. |
Practices: | In general it is good practice to reserve the +5Vdc power supply |
| exclusively for the task of powering one or more BASIC I/O ADs. As |
| with any microprocessor based equipment, reasonably clean power is |
| required for reliable operation. Sharing power with other devices such as |
| field signal transducers and contact excitation should be avoided |