Installing A Blade

1.If you are installing a new blade, remove the plastic cover from the I/O connector(s) and save for future use.

2.Orient the blade so that the blade handle is on the left side of the blade.

CAUTION: If you are installing a full-height blade in bays 3 or 4 or a half-height blade in bays 11 or 12, rotate the LCD module to the horizontal storage position to prevent accidental damage to the LCD screen.

3.To install a full-height blade or a half-height blade in bays 1 through 8, align the guide rail on the upper edge of the blade so that the rail fits between the plastic guides on the enclosure.

4.To install a half-height blade in one of the eight lower bays (bays 9 through 16), align the edge of the blade with the guide rail on the floor of the M1000e enclosure.

5.Slide the blade into the enclosure until the handle engages and locks the blade in place.

Power Supply Modules

The Dell PowerEdge M1000e enclosure supports up to six hot-swappable power supply modules, accessible from the enclosure back panel.

NOTE: The power supply modules have internal fans that provide thermal cooling to these modules. A power supply module must be replaced if an internal fan failure occurs.

The CMC module controls power management for the system. You can program the CMC to configure the power budget, redundancy, and dynamic power of the entire enclosure (chassis, servers, I/O modules, iKVM, CMC, and power supplies). The power management service optimizes power consumption and re-allocates power to different modules based on real-time demand. For more information, see the CMC User's Guide at support.dell.com/manuals.

NOTE: The wattage of a power supply module is listed on its regulatory label.

Power Supply Blanks

If the M1000e enclosure is operated with only three power supplies, power supply blanks must be installed in the three unoccupied power supply bays (4 through 6) to maintain proper cooling airflow in the enclosure.

AC Power Supply Modules

NOTE: A 2700 W power supply module requires 110 V to 240 V input from an AC power source. If a power supply module is plugged into a 110 V electrical outlet, the power supply operates at 1350 W, if you select the Allow 110 VAC Operation check box in the CMC Power Configuration screen.

NOTE: A 3000 W power supply module requires 200 V to 240 V input from an AC power source.

NOTE: PDU inlet cords for this system may be too thick to fit in the wire guides installed in the rack vertical rails. If this is the case, remove the wire guides by removing the attachment screw securing each guide. Route the PDU inlet cords along the vertical rails, securing them with tie wraps or strips.

71

Image 71
Contents Regulatory Model BMX01 Dell Inc. All Rights Reserved Contents General I/O Module Configuration Guidelines Configuring The I/O ModulesModules-Pass-Through Installing Enclosure ComponentsGetting Help Troubleshooting The EnclosureTechnical Specifications System Overview About Your SystemBlade Numbering Full Height Blades Control-Panel Features System Control-Panel FeaturesLCD Module LCD Display LCD Module FeaturesCenter button Configuration WizardUsing The LCD Module Menus KeyAction Left and right arrows Move between screensBack-Panel Features Back-Panel FeaturesBack-Panel Module Bay Numbering Power Supply IndicatorsSupply DC power to the systemPower supply fault indicator Icon Description AC power source Icon Present indicator DescriptionIndicator Description Fan power indicator Solid Green Fan Module IndicatorsAvocent Analog iKVM Switch Module Indicators Avocent iKVM Analog Switch Module OptionalGreen Avocent Analog iKVM Switch Module FeaturesLink indicator Off CMC Module CMC Module FeaturesCMC network cable CMC Fail-Safe ModeCondition Description CMC removal ConditionDescription Daisy-Chain CMC Network ConnectionOther Information You May Need System MessagesPage Page Before You Begin Initial Setup SequenceInitial CMC Network Configuration Configuring The CMC Using a Management Station And CLI Configuring The CMC Using The LCD Configuration WizardHttps//CMC IP addressport number Logging In To The CMC Using The Web-Based InterfaceHttps//CMC IP address Adding And Managing CMC Users Configuring iDRAC Networking Using The Web-Based InterfaceClick Setup → Deploy Setting The First Boot Device For ServersConfiguring And Managing Power Installing Or Updating The CMC FirmwareDownloading The CMC Firmware Updating The CMC Firmware Using The Web-Based InterfaceUpdating The iKVM Firmware Configuring The Optional iKVM Switch ModuleUpdating The CMC Firmware Using Racadm Tiering The Avocent iKVM Switch From a Digital KVM SwitchClick Setup → Devices → Device Modify Tiering The Avocent iKVM Switch From An Analog KVM SwitchConfiguring The Analog Switch Viewing And Selecting Servers FlexAddress Plus FlexAddressFabric a General I/O Module Configuration GuidelinesNetwork Information ConnectivityFabric C Fabric BHalf-Height Blades PowerEdge M610x OnlyMezzanine Cards Full-Height BladesEthernet switch Dual-Port Mezzanine Cards Module Port Mapping-Full-Height BladesStandard LOM Dual-Port Mapping Blade Module Mezzanine Card C Port Mezzanine Card B Example of PowerEdge M610x Port Mapping BladeBlade Module Blade Module Quad-Port Mezzanine Cards Portn+16 Module Port MappingHalf-Height Blades Example of Half-Height Blade Port Mapping Blade n Module Modules-SwitchesBrocade M6505 16 Gbps FC SAN I/O Module Brocade M6505 16 Gbps FC SAN I/O ModuleCisco Nexus B22 Fabric Extender Module Dell PowerEdge M I/O Aggregator SwitchDell PowerEdge M I/O Aggregator Switch Dell Force10 MXL 10/40 GbE SwitchDell Force10 MXL 10/40 GbE Switch I/O Module Mellanox M4001F/M4001Q/M4001T Infiniband Switch I/O ModuleMellanox M4001F/M4001Q/M4001T Infiniband Switch Module Dell PowerConnect KR 8024-k SwitchDell PowerConnect KR 8024-k Switch Dell PowerConnect M8428-k 10 Gb Converged Network SwitchDell PowerConnect M8428-k 10 Gb Converged Network Switch Mellanox M2401G DDR Infiniband Switch I/O ModuleMellanox M2401G DDR Infiniband Switch Module Mellanox M3601Q QDR Infiniband Switch I/O ModuleMellanox M3601Q QDR Infiniband Switch I/O Module Cisco Catalyst Ethernet Switch I/O ModulesCisco Catalyst Ethernet Switch Module Features Dell PowerConnect M6348 1 Gb Ethernet Switch I/O ModulePowerConnect M6348 1 Gb Ethernet Switch I/O Module Features Dell PowerConnect M6220 Ethernet Switch I/O ModulePowerConnect M6220 Ethernet Switch I/O Module Dell PowerConnect M8024 10 Gb Ethernet Switch I/O ModuleDell 8/4 Gbps FC SAN Module PowerConnect M8024 10 Gb Ethernet Switch I/O ModuleDell 8/4 Gbps FC SAN Module Brocade M5424 FC8 I/O ModuleBrocade M5424 FC8 I/O Module Indicator Status Off No signal carrier Amber onDell 4 Gbps Fibre Channel Pass-Through Module Modules-Pass-ThroughGreen on, three fast amber blinks 4 Gb link established With EmulexGreen on, one fast amber blink 1 Gb link established Green on, two fast amber blinks 2 Gb link establishedDell 10 GbE KR Pass-Through I/O Module 10/100/1000 Mb Ethernet Pass-Through I/O Module Dell 10 Gb Ethernet Pass-Through ModuleActivity indicators Power indicator Link indicators Page Removing a Blade Removing And Installing a BladeRecommended Tools Blade handle Guide rail on enclosure Release button AC Power Supply Modules Power Supply ModulesInstalling a Blade Power Supply BlanksRemoving An AC Power Supply Installing An AC Power Supply Wiring Instructions For a DC Power Supply DC Power Supply ModulesInput Requirements Assembling The DC Input Power Wires And DC Power Connector DC power socket Removing a DC Power Supply Installing a DC Power Supply Removing a Fan Module Fan ModulesRemoving a CMC Module Installing a Fan ModuleCMC Module SD Card Installing a CMC ModuleRemoving An iKVM Module Click the Power Management tabSelect the Reset CMC warm boot button IKVM ModuleModules Installing An iKVM ModuleRemoving An I/O Module Installing An I/O ModuleRemoving The Enclosure Bezel Enclosure BezelEnclosure Midplane Installing The Enclosure BezelRemoving The Front Module Cage Assembly And Midplane Front module cage assembly Removing and Installing the Midplane Installing The Midplane And Front Module Cage AssemblyRemoving The Control Panel Enclosure Control Panel AssemblyRemoving The LCD Module Installing The Control PanelRemoving and Installing the LCD Module Installing The LCD ModuleTroubleshooting Enclosure Components Troubleshooting The EnclosureTroubleshooting Power Supply Modules Troubleshooting a Wet EnclosureTroubleshooting I/O Modules Troubleshooting Fan ModulesTroubleshooting The iKVM Module Page Power Supply Module Enclosure SpecificationsEnclosure Control Panel Module SpecificationsOptional Avocent iKVM Module Chassis Management Controller ModuleBrocade M6505 16 Gbps FC SAN I/O Module Dell PowerEdge M I/O Aggregator Switch ModuleDell Force10 MXL 10/40 GbE Switch Module PowerConnect M6220 Ethernet Switch ModuleGb Ethernet Pass-Through Module Brocade FC8 Fibre Channel Switch ModuleBrocade FC4 Fibre Channel Switch Module Mellanox Infiniband Switch ModuleEnvironmental Ethernet switch I/O module Contacting Dell Getting Help
Related manuals
Manual 2 pages 36.05 Kb Manual 108 pages 15.26 Kb Manual 86 pages 34.71 Kb Manual 86 pages 40.45 Kb Manual 12 pages 5.14 Kb

M1000E specifications

The Dell M1000E blade enclosure is a robust and versatile platform designed to optimize data center efficiency and streamline server management. A fundamental component of Dell's PowerEdge series, the M1000E is engineered to house multiple server blades in a compact, modular chassis, enabling organizations to conserve space and reduce power consumption while enhancing performance.

One of the main features of the Dell M1000E is its ability to accommodate up to 16 half-height server blades or 8 full-height server blades. This flexibility allows for a diverse range of configurations tailored to specific workloads, whether for virtualization, database management, or application hosting. The chassis provides shared power supplies and cooling, further contributing to the enclosure's efficient operation.

In terms of connectivity, the M1000E includes integrated high-speed networking capabilities. It can support multiple generations of networking technologies, ranging from Gigabit Ethernet to 10 Gigabit Ethernet, and offers options for Fibre Channel and InfiniBand connections. This extensive range of networking options ensures that organizations can integrate the M1000E into existing infrastructures seamlessly.

The Dell M1000E also utilizes advanced management tools to simplify administration and monitoring. One of the standout features is the Dell OpenManage suite, which provides a comprehensive set of tools for hardware management and system updates. Users gain insights into system health, performance, and power usage, enabling proactive maintenance and optimization of resources.

The enclosure is designed with scalability in mind. As businesses grow, the M1000E can be expanded easily by adding more blades without the need for significant reconfiguration. This scalability ensures that IT departments can respond rapidly to changing demands, ensuring that resources align with organizational requirements.

From a security standpoint, the M1000E provides multiple layers of protection, including secure access controls and configurable management interfaces. This helps safeguard sensitive information and ensures compliance with stringent data protection regulations.

Overall, the Dell M1000E blade enclosure represents a compelling solution for modern data centers, merging performance, efficiency, and scalability into a single chassis designed to meet the demands of today’s enterprise environments. Its advanced technologies and features make it a valuable asset for organizations looking to enhance their IT infrastructure.