Minuteman UPS PRO-E user manual Turning the Unit ON/OFF, Self Test, DIP Switch Settings

Page 10

English

TURNING THE UNIT ON/OFF

ON / OFF / Test Button

Press and release the ON/OFF/Test Button after one beep to turn the UPS ON and supply power to the load. The load is immediately powered while the UPS runs a two-second self test. Press and release the ON/OFF/Test Button after one beep to turn the UPS OFF. The UPS will continue to charge the batteries whenever it is plugged into an AC outlet and there is AC present.

SELF TEST

The self test feature is useful to verify the correct operation of the UPS and the condition of the batteries. With the UPS in the normal On-Line mode, press and hold the ON/OFF/Test Button for approximately 4 seconds (four beeps), then release the button. The UPS will perform a ten-second self test. During the self test, the UPS will switch to battery power and the On-Line LED will blink and the audible alarm will sound. The length of the test that is automati- cally performed every two weeks is longer than the start-up or user invoked test. This test will run for approximately fifteen-seconds to measure the battery’s capability to provide an acceptable amount of runtime. If the UPS fails a self test, one of the LEDs will remain illuminated indicating the type of problem.

Note: The UPS will automatically perform a self test on start-up and every two weeks.

DIP SWITCH SETTINGS

The DIP Switch setting may be changed by the user to set the desired Inverter (on battery) output voltage. The DIP Switch must be set to the desired Inverter output voltage and then the UPS must be turned OFF and restarted to reconfigure the microprocessor and save the changes. The Inverter (on battery) output voltage setting for the 120V models can be either 120VAC (default) or 127VAC. Changing the Inverter output voltage to 127VAC, will also change the Buck setpoint from 130VAC (default) to 136VAC. The Inverter (on battery) output voltage setting for the 230V models can be either 230VAC (default) or 208VAC. Changing the Inverter output voltage to 208VAC, will also change the Boost1 setpoint from 206VAC (default) to 198VAC.

Inverter output voltage

Switch 1 2 120V (230V)

127V (208V)

9

Image 10
Contents PRO-E Series English Important Safety Instructions Authorized Service Personnel only Receiving Inspection English Rear Panel 120V ModelsInstallation Installation PlacementConnecting Your Equipment Charging the Battery Connecting the UPS to AN AC SourceChecking the Site Wiring Fault Communications Port Connection OptionalTurning the Unit ON/OFF DIP Switch SettingsSelf Test WEAK/BAD Battery Alarms On BatteryLOW Battery Warning UPS FaultCommunications Ports RS232 and USB If the AC circuit breaker trips Replacing the Battery Authorized Service Personnel onlyBattery Replacement Procedure PRO-E PRO500E PRO700EEnglish If the UPS Requires Service Model Number PRO500E PRO700E EPO English Limited Product Warranty Robert Calhoun Declaration of ConformityEnglish PN 34000226 Rev