9.Disconnect the positive (red) wire from the battery positve terminal.

10.Disconnect the battery negative (black) wire from the battery negative terminal.

NOTE: Use CAUTION, do not touch the battery positive wire to the battery negative wire.

11.Remove the battery bracket retaining screw and slide the battery bracket upwards.

12.Using the pull tab, pull the batteries out completely. DO NOT pull the batteries out by pulling the battery jumper wires.

13.Remove the battery jumper wires.

14.Verify proper polarity. Re-install the battery jumper wires on the new batteries.

15.Slide the new batteries into the battery compartment.

16.Re-install the battery bracket and the battery bracket retaining screw.

17.Verify proper polarity. Reconnect the battery negative (black) wire to the battery negative terminal.

18.Verify proper polarity. Reconnect the battery positive (red) wire to the battery positive terminal. Some sparking may occur, this is normal.

19.Re-install the front panel of the UPS.

20.Re-install the retaining screws for the front panel of the UPS.

21.Dispose of the old batteries properly at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries.

22.The UPS is now ready for the normal start-up operation.

NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the batteries, the user must initiate a self test to clear the Weak/Bad Battery Alarm. To initiate a self test see section 4 "SELF TEST".

15

Image 16
Contents PRO-E Series English Important Safety Instructions Authorized Service Personnel only Receiving Inspection English Rear Panel 120V ModelsInstallation Installation PlacementConnecting Your Equipment Connecting the UPS to AN AC Source Checking the Site Wiring FaultCharging the Battery Communications Port Connection OptionalTurning the Unit ON/OFF DIP Switch SettingsSelf Test Alarms On Battery LOW Battery WarningWEAK/BAD Battery UPS FaultCommunications Ports RS232 and USB If the AC circuit breaker trips Replacing the Battery Authorized Service Personnel onlyBattery Replacement Procedure PRO-E PRO500E PRO700EEnglish If the UPS Requires Service Model Number PRO500E PRO700E EPO English Limited Product Warranty Robert Calhoun Declaration of ConformityEnglish PN 34000226 Rev