English
9.Disconnect the positive (red) wire from the battery positve terminal.
10.Disconnect the battery negative (black) wire from the battery negative terminal.
NOTE: Use CAUTION, do not touch the battery positive wire to the battery negative wire.
11.Remove the battery bracket retaining screw and slide the battery bracket upwards.
12.Using the pull tab, pull the batteries out completely. DO NOT pull the batteries out by pulling the battery jumper wires.
13.Remove the battery jumper wires.
14.Verify proper polarity.
15.Slide the new batteries into the battery compartment.
16.
17.Verify proper polarity. Reconnect the battery negative (black) wire to the battery negative terminal.
18.Verify proper polarity. Reconnect the battery positive (red) wire to the battery positive terminal. Some sparking may occur, this is normal.
19.
20.
21.Dispose of the old batteries properly at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries.
22.The UPS is now ready for the normal
NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the batteries, the user must initiate a self test to clear the Weak/Bad Battery Alarm. To initiate a self test see section 4 "SELF TEST".
15