REPLACING THE BATTERY

(AUTHORIZED SERVICE PERSONNEL ONLY)

The PRO-E Series UPS has an easy to replace hot-swappable batteries. Please read all of the WARNINGS and CAUTIONS before attempting to service the batteries.

NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up.

WARNING! This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond battery replacement procedures below. This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed by AUTHORIZED SERVICE PERSONNEL ONLY.

CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.

CAUTION: Do not dispose of batteries in a fire. The batteries may explode. The batteries in this UPS are recyclable. Dispose of the batteries properly. The batteries contain lead and pose a hazard to the

environment and human health if not disposed of properly. Refer

to local codes for proper disposal requirements or return the battery to MINUTEMAN.

CAUTION: Although battery system voltages are only 12VDC, 24VDC, and 36VDC the battery system can still present a risk of electrical shock. The current capability of a battery is sufficient to burn wire

or tools very rapidly, producing molten metal. Observe these precautions when replacing the batteries:

1.Remove watches, rings, or other metal objects.

2.Use hand tools with insulated handles.

3.Wear protective eye gear (goggles), rubber gloves and boots.

4.Do not lay tools or other metal parts on top of batteries.

5.Disconnect the charging source prior to connecting or disconnecting the battery terminals.

6.Determine if the battery is inadvertently grounded. If the battery is, remove the source of the grounding. Contact with any part of a grounded battery can result in an electrical shock. The likehood of such shock will be reduced, if such grounds are removed during installation and maintenance.

13

Image 14
Contents PRO-E Series English Important Safety Instructions Authorized Service Personnel only Receiving Inspection English Rear Panel 120V ModelsConnecting Your Equipment Installation PlacementInstallation Charging the Battery Connecting the UPS to AN AC SourceChecking the Site Wiring Fault Communications Port Connection OptionalSelf Test DIP Switch SettingsTurning the Unit ON/OFF WEAK/BAD Battery Alarms On BatteryLOW Battery Warning UPS FaultCommunications Ports RS232 and USB If the AC circuit breaker trips Replacing the Battery Authorized Service Personnel onlyBattery Replacement Procedure PRO-E PRO500E PRO700EEnglish If the UPS Requires Service Model Number PRO500E PRO700E EPO English Limited Product Warranty Robert Calhoun Declaration of ConformityEnglish PN 34000226 Rev