Minuteman UPS PRO-E user manual Model Number PRO500E PRO700E

Page 18

English

MODEL NUMBER

PRO500E

PRO700E

PRO1100E

PRO1500E

(230V Models)

(PRO500iE)

(PRO700iE)

(PRO1100iE)

(PRO1500iE)

Acceptable Input voltage

 

0 - 165VAC

(0 - 290VAC)

 

Input voltage (AC Mode)

 

75 - 145VAC (150 - 280VAC)

 

Output voltage (AC Mode)

120VAC: 105-130VAC

(230VAC: 206-250VAC)

Nominal input frequency

 

50 or 60 Hz, autosensing

 

Input protection

 

Resettable circuit breaker

 

Frequency limits (AC Mode)

 

50 or 60 Hz, +/-6Hz

 

Transfer time

 

2-6 mS typical

 

Maximum load

500VA

700VA

1100VA

1500VA

 

350W

490W

770W

1050W

On-battery output voltage

Default 120V (230V) / User

selectable at 120/127V, (208/230V)

On-battery frequency

50/60 Hz, +/-.5 Hz, unless synchronized to utility

On-battery waveshape

 

Simulated Sine Wave

 

Protection

Over current, short circuit protected and latching shutdown

Surge energy rating (one time,

 

500 J (440 J)

 

10/1000 uS waveform)

 

 

 

 

 

Surge current capability

 

6500 Amps total

 

(one time, 8/20 uS waveform)

 

 

Surge response time

0 ns (instantaneous) normal mode; <5 ns common mode

Surge voltage let-through (as

 

<5%

 

a percentage of an applied

 

 

ANSI C62.41 Cat. A +/-6 kV)

 

 

 

 

 

Noise filter

Normal and common mode EMI/RFI suppression

Battery type: Sealed, non-

1-12V9Ah

2-12V7Ah

3-12V7Ah

3-12V9Ah

spillable, maintenance free,

lead-acid

 

 

 

 

 

Typical battery life

3-5 years, depending on discharge cycles and ambient temp

Typical recharge time

 

8 hours from total discharge

 

10 Base-T surge protection let-

 

 

 

 

 

through (as a percentage of

 

<5%

 

an applied +/-6 kV 1.2/50 us,

 

 

500 a 8/20 uS test)

 

 

 

 

 

Telephone line surge protec-

 

 

 

 

 

tion let-through (as a percent-

 

<1%

 

age of an applied +/-6 kV 1.2/

 

 

 

 

 

 

 

50 us, 500a 8/20 uS test)

 

 

 

 

 

Runtime: Half Load

15-Minutes

17-Minutes

 

16-Minutes

14-Minutes

Runtime: Full Load

4-Minutes

5-Minutes

 

5-Minutes

4.5-Minutes

Electromagnetic immunity

IEC 801-2 level IV, 801-4 level IV, 801 -5 level III

Audible noise at 1 m (3 ft.)

 

<45 dBA

 

Size - Net

7.56 x 12.56 x 6.38"

8.03 x 16.18 x 6.38"

H X D X W

192 x 319 x 162 mm

204 x 411 x 162 mm

Size - Shipping

13 x 18.9 x 11.4"

13 x 22.8 x 12.6"

H X D X W

330 x 480 x 290 mm

330 x 580 x 320 mm

Weight - Net (Shipping)

20.3 (23)lb

27.33 (30)lb

39.24 (43)lb

42.33 (47)lb

9.2 (10.4)Kg

12.4 (13.6)Kg

17.8 (19.5)Kg

19.2 (20.9)Kg

 

Safety and approvals

UL1778, cUL (CSA

22.1), TUV; 230V models

EMC Verification

 

FCC Class B, CE certified

 

17

Image 18
Contents PRO-E Series English Important Safety Instructions Authorized Service Personnel only Receiving Inspection English Rear Panel 120V ModelsInstallation Placement InstallationConnecting Your Equipment Charging the Battery Connecting the UPS to AN AC SourceChecking the Site Wiring Fault Communications Port Connection OptionalDIP Switch Settings Turning the Unit ON/OFFSelf Test WEAK/BAD Battery Alarms On BatteryLOW Battery Warning UPS FaultCommunications Ports RS232 and USB If the AC circuit breaker trips Replacing the Battery Authorized Service Personnel onlyBattery Replacement Procedure PRO-E PRO500E PRO700EEnglish If the UPS Requires Service Model Number PRO500E PRO700E EPO English Limited Product Warranty Robert Calhoun Declaration of ConformityEnglish PN 34000226 Rev