Minuteman UPS PRO-E user manual Communications Ports RS232 and USB

Page 12

COMMUNICATIONS PORTS (RS232 and USB)

The RS232 communication port is a standard DB9 female with both RS232 and simulated contact closure capability. The PRO-E series UPS will poll the port and activate the port for RS232 or contact closure in accordance with the type of cable it finds connected to the port. To change the port configuration requires the unit be turned off and restarted with the desired cable connected. The pinout for the port is depicted per the chart below.

Pin 1: EPO Emergency Power Off (pull and hold this pin low to turn off the UPS, release this pin from low to turn to restart the UPS)

Pin 2: /TXD

Pin 3: /RXD and receive ups shutdown command

Pin 4: Simulated contact closure AC fail, NO

Pin 5: Ground

Pin 6: Simulated contact closure low battery warning, NO

Pin 7: Simulated contact closure AC fail, NC

Pin 8: AC fail signal (high to low signal)

Pin 9: Not Used

NOTE: See the SentryII CD for the Power Monitoring Software installation. See the USB Driver CD for the USB installation.

English

11

Image 12
Contents PRO-E Series English Important Safety Instructions Authorized Service Personnel only Receiving Inspection English Rear Panel 120V ModelsInstallation Placement InstallationConnecting Your Equipment Connecting the UPS to AN AC Source Checking the Site Wiring FaultCharging the Battery Communications Port Connection OptionalDIP Switch Settings Turning the Unit ON/OFFSelf Test Alarms On Battery LOW Battery WarningWEAK/BAD Battery UPS FaultCommunications Ports RS232 and USB If the AC circuit breaker trips Replacing the Battery Authorized Service Personnel onlyBattery Replacement Procedure PRO-E PRO500E PRO700EEnglish If the UPS Requires Service Model Number PRO500E PRO700E EPO English Limited Product Warranty Robert Calhoun Declaration of ConformityEnglish PN 34000226 Rev