Minuteman UPS ED6000T, ED6200T user manual Led Lcd

Page 16

3.6.5.10When all of the setting changes are complete, press the enter keypad to save all the changes. Then the LCD screen will display drawing Z, then the LCD screen will change to drawing AA to confirm the changes. If you

do not want to save the changes press the “OFF” keypad for 5- seconds, then the LCD screen turns to Drawing AA, which means your changes were not saved.

3.6.5.11Turn Off the input circuit breaker on the rear panel of the UPS module.

3.6.5.12The changes to the Settings are complete.

Z

* Press the Enter keypad to save the data.

AA

*It shows the UPS is locked.

3.6.6UPS Is Off Due to Unknown Reason

3.6.6.1If a serious abnormal condition occurred, the UPS will lock it itself in the “OFF” position as shown in drawing AA and a error message will be displayed on the LCD screen.

3.6.6.2After 3 seconds, all messages will be locked except the Bypass messages

(LED

& LCD

). If the utility voltage is abnormal after the UPS is

locked,

the LED

will be extinguished and the LCD

will be

shown on the LCD screen.

 

3.6.6.3Check the error messages then see section 4 to troubleshoot the problem or see section 8 Obtaining Service. To unlock the UPS press the OFF

switch for 5-seconds and the audible alarm will sound 2-beeps. Turn Off the input circuit breaker on the rear panel of the UPS. The UPS will be unlocked now, but the original problem may not be resolved, see section 8 Obtaining Service.

28

3.6.7Turning Off the UPS

3.6.7.1Press the Off switch for approximately 5-seconds, the Inverter will turned off, the UPS will transfer to the Bypass mode and the LCD screen will display drawing B.

3.6.7.2Turn Off the input circuit breaker on the rear panel of the UPS.

3.6.7.3Turn Off the DC circuit breaker on the rear panel of the Battery Pack.

3.6.7.4The UPS is OFF.

3.6.7.5To completely de-energize the UPS, disconnect the battery cable from the rear panel of the UPS. Turn Off the utility circuit breaker at the service panel.

3.6.8Maintenance Bypass Procedure

3.6.8.1The Maintenance Bypass Switch is for the maintenance of the UPS module only. The maintenance of the UPS module must be done by QUALIFIED SERVICE PERSONNEL ONLY. MINUTEMAN accepts no liabilities and is not limited to: injury to the Service Personnel, or damages to; the UPS system, or the connected equipment caused by the incorrect servicing of the UPS system.

3.6.8.1.1Press the Off switch for approximately 5-seconds, the LCD screen will display drawing B and the UPS will be in the Bypass mode.

3.6.8.1.2Remove the Maintenance Bypass Switch cover from the Maintenance Bypass Switch on the rear panel of the UPS.

3.6.8.1.3Turn the Maintenance Bypass Switch to the “Bypass” position. The

LCD screen will display the maintenance sign at the upper right- hand corner of the LCD screen.

3.6.8.1.4Turn off the UPS’s input circuit breaker on the rear panel of the UPS.

3.6.8.1.5Remove the cover from the UPS.

NOTE: The Input utility voltage is still present at the input filter board and at the terminal block. Use Caution.

3.6.8.1.6Disconnect the battery positive (Red) wire from the battery positive terminal and place a piece of black electrical tape over end of the battery positive (Red) wire.

3.6.8.1.7The UPS is ready for maintenance.

3.6.8.1.8Once the servicing of the UPS is complete, remove the black electrical tape from the end of the battery positive (Red) wire and reconnect the battery positive (Red) wire to the battery positive terminal.

3.6.8.1.9Re-install the UPS cover.

3.6.8.1.10Turn on the UPS’s input circuit breaker.

3.6.8.1.11Turn the Maintenance Bypass Switch to the “INV” position. The UPS will transfer to the normal Bypass mode.

29

Image 16
Contents ED6000T & ED6200T Parallel RedundantTable of Contents Important Safety Instruction An Important NoticeLife Support Policy FCC NoticeProduct Introduction EPO Controls and Indicators Installation and Operation Qualified Service Personnel onlyRear Panel UnpackingInstallation of the Caster Covers Installation PlacementStorage Instruction Wiring the Input and Output Connections AWGPage Operation and Setup Instructions Page It shows the UPS is providing power to the load It shows the Internal Temperature of the UPS System Page LED LCD Power Monitoring Software EPO Emergency Power Off PortCommunication Port, EPO Port and Option Cards RS232 Communication PortService Personnel only Troubleshooting GuideReplacing the Batteries Battery Replacement Procedure Page Physical SpecificationsRegulatory Compliance Obtaining Service Limited Product WarrantyDeclaration of Conformity

ED6200T, ED6000T specifications

The Minuteman UPS ED6000T and ED6200T are robust uninterruptible power supply (UPS) systems designed to offer reliable protection for sensitive electronic equipment. These units stand out in the market for their enhanced features, advanced technologies, and exceptional performance.

The core design of the ED6000T and ED6200T integrates a pure sine wave output, ensuring compatibility with all types of devices, including sensitive electronics and critical infrastructure. This feature minimizes electrical distortion, providing protection against damage from power fluctuations. They deliver up to 6000VA and 6200VA of power respectively, making them suitable for small to medium-sized data centers, telecommunications equipment, and critical servers.

One key characteristic of these models is their comprehensive LCD display that provides real-time monitoring of UPS status, battery charge level, load percentage, and other essential diagnostics. This user-friendly interface makes it convenient for users to assess performance at a glance and manage their power protection strategies effectively.

Both models employ advanced battery management technologies, including Smart Battery Management that extends battery life through optimized charging cycles. This is crucial for maintaining reliability, especially in environments where power outages can be frequent and disruptive. The UPS units also feature an automatic voltage regulation (AVR) system that corrects minor voltage fluctuations, maintaining consistent output without switching to battery mode.

Additionally, the ED6000T and ED6200T incorporate the Minuteman Green Power UPS™ technology, designed to minimize energy consumption and reduce heat output, thus contributing to lower operational costs and environmental sustainability. With an energy-efficient design, they are not only financially beneficial but also eco-friendly.

Connectivity options are another highlight, as both models feature multiple outlets, including surge-protected and battery backup outlets, ensuring plenty of connections for various devices. They are equipped with USB and serial communication ports that allow for seamless integration with monitoring and management software, thereby enhancing their functionality in networked environments.

In conclusion, the Minuteman UPS ED6000T and ED6200T are powerful solutions for businesses seeking reliable power protection. With their pure sine wave output, advanced battery management, user-friendly interfaces, and energy-efficient designs, they represent a solid investment for safeguarding critical electronics against power interruptions.