Minuteman UPS ED6200T, ED6000T user manual Wiring the Input and Output Connections, Awg

Page 9

3.5.Wiring the Input and Output Connections

(Qualified Electrical Contractor Only)

3.5.1A Qualified Electrical Contractor must perform the hardwiring when connecting the Input and Output wires to the terminal block on the ED6000T UPS. Apply 22.1lb-in of torque force when connecting to the terminal blocks. The Input and Output of the UPS MUST be Hardwired.

3.5.1.1 INPUT connections for the ED6000T Hardwired only:

1.Connect L1 from the utility to terminal L12.

2.Connect L2 from the utility to terminal N1.

3.Connect the earth ground from the utility to terminal G1.

CAUTION - To reduce the risk of fire, connect the UPS Utility input to a branch circuit with an over-current protection of 40 amperes in accordance with the National Electric Code, ANSI/NFPA 70. Use No. 8 AWG, 60°C copper wire and apply 22.1lb-in of torque force when connecting to the terminal blocks.

3.5.1.1.1OUTPUT connections for ED6000T Hardwired only:

Configurations #1 – #7 are for Hardwiring the output of ED6000T. A Qualified Electrical Contractor must perform the hardwiring. The outputs must be connected to an over-current protection device (circuit breaker) in accordance with the National Electric Code, ANSI/NFPA 70. Use 60°C copper wire and apply 22.1lb-in of torque force when connecting to the terminal blocks.

Output Voltage and Load

Output Circuit Breaker

Wire

208V

& 240V / 6KVA

30 Amps

10 AWG

120V

/ 3KVA

30 Amps

10 AWG

120V

/ 6KVA

50 Amps

6 AWG

3.5.1.1.2Configuration # 1:

Output: Two 120VAC 3KVA circuits (3KVA max load per circuit). Total combined output load not to exceed 6KVA.

1.Circuit1 (120VAC): L22 - Line, N22 - Neutral, G2 - Ground.

2.Circuit2 (120VAC): L21 - Line, N21 - Neutral, G2 - Ground.

3.5.1.1.3Configuration # 2:

Output: One 120VAC 6KVA circuit. Total output load not to exceed 6KVA.

1.Connect a jumper wire from L22 to L21.

2.Connect a second jumper wire from N22 to N21.

3.Circuit1 (120VAC): L22 - Line, N22 - Neutral, G2 - Ground.

14

15

Image 9
Contents Parallel Redundant ED6000T & ED6200TTable of Contents An Important Notice Important Safety InstructionLife Support Policy FCC NoticeProduct Introduction EPO Controls and Indicators Qualified Service Personnel only Installation and OperationRear Panel UnpackingInstallation Placement Installation of the Caster CoversStorage Instruction AWG Wiring the Input and Output ConnectionsPage Operation and Setup Instructions Page It shows the UPS is providing power to the load It shows the Internal Temperature of the UPS System Page LED LCD EPO Emergency Power Off Port Power Monitoring SoftwareCommunication Port, EPO Port and Option Cards RS232 Communication PortTroubleshooting Guide Service Personnel onlyReplacing the Batteries Battery Replacement Procedure Page Specifications PhysicalRegulatory Compliance Limited Product Warranty Obtaining ServiceDeclaration of Conformity

ED6200T, ED6000T specifications

The Minuteman UPS ED6000T and ED6200T are robust uninterruptible power supply (UPS) systems designed to offer reliable protection for sensitive electronic equipment. These units stand out in the market for their enhanced features, advanced technologies, and exceptional performance.

The core design of the ED6000T and ED6200T integrates a pure sine wave output, ensuring compatibility with all types of devices, including sensitive electronics and critical infrastructure. This feature minimizes electrical distortion, providing protection against damage from power fluctuations. They deliver up to 6000VA and 6200VA of power respectively, making them suitable for small to medium-sized data centers, telecommunications equipment, and critical servers.

One key characteristic of these models is their comprehensive LCD display that provides real-time monitoring of UPS status, battery charge level, load percentage, and other essential diagnostics. This user-friendly interface makes it convenient for users to assess performance at a glance and manage their power protection strategies effectively.

Both models employ advanced battery management technologies, including Smart Battery Management that extends battery life through optimized charging cycles. This is crucial for maintaining reliability, especially in environments where power outages can be frequent and disruptive. The UPS units also feature an automatic voltage regulation (AVR) system that corrects minor voltage fluctuations, maintaining consistent output without switching to battery mode.

Additionally, the ED6000T and ED6200T incorporate the Minuteman Green Power UPS™ technology, designed to minimize energy consumption and reduce heat output, thus contributing to lower operational costs and environmental sustainability. With an energy-efficient design, they are not only financially beneficial but also eco-friendly.

Connectivity options are another highlight, as both models feature multiple outlets, including surge-protected and battery backup outlets, ensuring plenty of connections for various devices. They are equipped with USB and serial communication ports that allow for seamless integration with monitoring and management software, thereby enhancing their functionality in networked environments.

In conclusion, the Minuteman UPS ED6000T and ED6200T are powerful solutions for businesses seeking reliable power protection. With their pure sine wave output, advanced battery management, user-friendly interfaces, and energy-efficient designs, they represent a solid investment for safeguarding critical electronics against power interruptions.