1 Important Safety Instruction

1.1.An Important Notice

1.1.1To ensure safety in all applications where a UPS system is hardwired to the electrical supply the UPS must be installed by a Qualified Electrical Contractor.

1.1.2The UPS has its own internal energy source (battery). If the UPS is switched on when there is no AC power is available, there could be voltage at the output terminals.

1.1.3Servicing of the UPS system must be performed by Qualified Service Personnel ONLY. MINUTEMAN accepts no liabilities and is not limited to: injury to the Service Personnel, or damages to; the UPS system, or the connected equipment caused by the incorrect installation or servicing of the UPS system.

1.1.4Make sure that the input voltage rating of the UPS matches the supply voltage.

1.1.5This UPS series is intended to be install in a temperature controlled environment that is free of conductive contaminants. Select a location that will provide good air circulation for the UPS at all times. Avoid locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight. Route power cords so they cannot be walked on or damaged.

1.1.6To eliminate overheating of the UPS, keep all ventilation openings free from obstruction, and do not store anything on top of the UPS system. Keep the UPS system at least 12” (30 cm) away from the wall.

1.1.7The battery will discharge naturally if the UPS is unused for any length of time. The batteries should be recharged every 2-3 months if unused.

1.1.8This UPS supports electronic equipment in offices, telecommunications, process control, and medical applications.

1.1.9Risk of Electrical Shock. Make sure the UPS is completely turned off when moving the UPS from one location to another.

1.1.10The UPS has a Maintenance Bypass Switch. Follow the procedures to perform the maintenance bypass operation.

1.1.11SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during the Installation and the Maintenance of the UPS and batteries.

1.1.12CAUTION - A disconnect switch must be provided by the user for the AC output circuit when the UPS’s output is hardwired. To reduce the risk of fire, connect only to a circuit provided with branch circuit over-current protection (30 amperes for 208/240V output or 50 amperes for single 120V output) in accordance with the National Electric Code, ANSI/NFPA 70.

1.1.13CAUTION - To reduce the risk of fire, connect the input to a circuit provided with branch circuit over-current protection for 40 amperes in accordance with the National Electric Code, ANSI/NFPA 70. Use No. 8 AWG, 60°C copper wire and 22.1lb-in Torque force when connecting to terminal block.

1.1.14CAUTION - To reduce the risk of electrical shock with the installation of this UPS system and the connected equipment, the installer must ensure that the combined sum of the AC leakage current does not exceed 3.5mA.

1.1.15WARNING - This Uninterruptible Power Supply (UPS) contains potentially hazardous voltages. Do not attempt to disassemble the UPS system beyond the battery replacement procedure. This UPS system contains no user serviceable parts. QUALIFIED SERVICE PERSONNEL ONLY must perform the maintenance and the battery replacement for this UPS system.

1.2.Life Support Policy

As a general policy, we do not recommend the use of any of our products in life support applications where failure or malfunction of the product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. We do not recommend the use of any of our products in direct patient care. We will not knowingly sell our products for use in such applications unless it receives in writing assurances satisfactory to us that (a) the risks of injury or damage have been minimized,

(b)the customer assumes all such risks, and (c) our liability is adequately protected under the circumstances.

1.3.FCC Notice

This equipment has been tested and found to comply with the limits for a Class A computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules and the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference of the Canadian Department of Communications.

2

3

Image 3
Contents Parallel Redundant ED6000T & ED6200TTable of Contents FCC Notice Important Safety InstructionAn Important Notice Life Support PolicyProduct Introduction EPO Controls and Indicators Unpacking Installation and OperationQualified Service Personnel only Rear PanelInstallation Placement Installation of the Caster CoversStorage Instruction AWG Wiring the Input and Output ConnectionsPage Operation and Setup Instructions Page It shows the UPS is providing power to the load It shows the Internal Temperature of the UPS System Page LED LCD RS232 Communication Port Power Monitoring SoftwareEPO Emergency Power Off Port Communication Port, EPO Port and Option CardsTroubleshooting Guide Service Personnel onlyReplacing the Batteries Battery Replacement Procedure Page Specifications PhysicalRegulatory Compliance Limited Product Warranty Obtaining ServiceDeclaration of Conformity

ED6200T, ED6000T specifications

The Minuteman UPS ED6000T and ED6200T are robust uninterruptible power supply (UPS) systems designed to offer reliable protection for sensitive electronic equipment. These units stand out in the market for their enhanced features, advanced technologies, and exceptional performance.

The core design of the ED6000T and ED6200T integrates a pure sine wave output, ensuring compatibility with all types of devices, including sensitive electronics and critical infrastructure. This feature minimizes electrical distortion, providing protection against damage from power fluctuations. They deliver up to 6000VA and 6200VA of power respectively, making them suitable for small to medium-sized data centers, telecommunications equipment, and critical servers.

One key characteristic of these models is their comprehensive LCD display that provides real-time monitoring of UPS status, battery charge level, load percentage, and other essential diagnostics. This user-friendly interface makes it convenient for users to assess performance at a glance and manage their power protection strategies effectively.

Both models employ advanced battery management technologies, including Smart Battery Management that extends battery life through optimized charging cycles. This is crucial for maintaining reliability, especially in environments where power outages can be frequent and disruptive. The UPS units also feature an automatic voltage regulation (AVR) system that corrects minor voltage fluctuations, maintaining consistent output without switching to battery mode.

Additionally, the ED6000T and ED6200T incorporate the Minuteman Green Power UPS™ technology, designed to minimize energy consumption and reduce heat output, thus contributing to lower operational costs and environmental sustainability. With an energy-efficient design, they are not only financially beneficial but also eco-friendly.

Connectivity options are another highlight, as both models feature multiple outlets, including surge-protected and battery backup outlets, ensuring plenty of connections for various devices. They are equipped with USB and serial communication ports that allow for seamless integration with monitoring and management software, thereby enhancing their functionality in networked environments.

In conclusion, the Minuteman UPS ED6000T and ED6200T are powerful solutions for businesses seeking reliable power protection. With their pure sine wave output, advanced battery management, user-friendly interfaces, and energy-efficient designs, they represent a solid investment for safeguarding critical electronics against power interruptions.