[Connections and Settings in Torque Control Mode]
Signal | Pin No. | Symbol |
|
|
|
|
| Function | I/F circuit | ||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
Command pulse | 33 | INH |
| The function differs depending on the control mode. | SI | ||||||||
input inhibit |
|
|
|
|
|
|
|
|
|
|
|
| page 134 |
| Position control |
| • Enter command pulse input inhibit. |
| |||||||||
|
|
|
|
| |||||||||
|
|
|
|
| • You can disable this input with Pr43 |
|
| ||||||
|
|
|
|
| (disable command pulse input inhibit). |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Pr43 value | Meaning |
|
|
| ||
|
|
|
|
|
|
| The INH signal (input) is disabled. |
|
|
| |||
|
|
|
|
|
|
|
| 0 | • With COM– closed, the pulse |
|
|
| |
|
|
|
|
|
|
|
|
|
| command signal (PULSE SIGN) is |
|
|
|
|
|
|
|
|
|
|
|
|
| enabled. |
|
|
|
|
|
|
|
|
|
|
|
|
| • With COM– open, the pulse |
|
|
|
|
|
|
|
|
|
|
|
|
| command signal (PULSE SIGN) is |
|
|
|
|
|
|
|
|
|
|
|
|
| inhibited. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Speed control |
| • With speed setting of the 1st selection input, you can set 4 |
|
| |||||||
|
|
|
|
| speeds in combination with CL input. |
|
| ||||||
|
|
|
|
| • For details, see Pr05 (Speed |
|
| ||||||
|
| Torque control |
| • Invalid |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Speed zero clamp | 26 | ZEROSPD | • With COM– open, the speed command is considered zero. | SI | |||||||||
|
|
|
|
|
| • This input can be made disabled using Pr06. | page 134 | ||||||
|
|
|
|
|
| • With factory setting, disconnecting this pin from COM– sets |
| ||||||
|
|
|
|
|
|
| the speed to zero. |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| Pr06 value | Meaning |
|
|
| ||
|
|
|
|
|
|
| 0 | ZEROSPD is disabled. |
|
|
| ||
|
|
|
|
|
|
|
| 1 | ZEROSPD is enabled. |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Gain switching | 27 | GAIN |
| • This is setting of Pr30 (2nd gain setting) and has the | SI | ||||||||
|
|
|
|
|
|
| following 2 types of functions: | page 134 | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Pr30 value |
| Connection |
|
| Function |
|
| ||||
|
|
| to COM- |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
| 0 |
|
| Open |
| Speed loop: PI (Proportional / Integral) action |
|
| |||
|
|
|
| Close |
| Speed loop: P (Proportional) action |
|
| |||||
|
|
|
|
|
| Open |
| • 1st gain selected (Pr10, 11, 12, 13 and 14) |
|
| |||
|
|
| 1 |
|
| Close |
| • 2nd gain selected (Pr18, 19, 1A, 1B, 1C) |
|
| |||
|
|
|
|
| To use the second gain, set Pr31 to “2”. |
|
| ||||||
|
|
|
|
|
| • No.2 Gain change Funcutions, see page 202 "Adjustments ". |
| ||||||
Alarm clear | 31 |
|
| • If the COM- connection is kept closed for more than 120 | SI | ||||||||
|
|
|
|
|
|
| ms, the alarm status will be cleared. | page 134 | |||||
|
|
|
|
|
| • For details about not cleared alarm, see page 216 |
| ||||||
|
|
|
|
|
|
| "Protective Functions". |
|
Torque Control Mode
Connections and Settings in