MGE UPS Systems Galaxy PW user manual System start-up, Start-up of a module

Page 21

start-up

User’s Manual

system start-up

single-UPS unit or redundant parallel UPS

See figure 15.

Proceed in the following order:

close the upstream switches supplying normal and bypass AC source power (on the LV switchboard);

close normal AC input switch Q1. The system powers up:

the rectifier/charger automatically starts, green light 1 on the control panel goes on,

light 2 turns red;

close bypass AC input switch Q4S:

green lights 3 and 5 on the control panel go on;

close inverter output switch Q5N; close battery circuit breaker QF1;

light 2 goes off;

open maintenance bypass switch Q3BP;

press the "inverter on" button 7 on the control panel:

the green "inverter" light 4 flashes,

the inverter starts, then, if the bypass AC source transfer conditions are satisfied, the load is transferred to the inverter if the on-line mode is selected.

the green "static-bypass" light 3 goes off,

the green "inverter" light 4 shines for on-line mode.

parallel UPS unit for increased output

See figure 16.

Proceed in the following order:

check that all load devices are off or that the load is disconnected;

close the upstream switch supplying normal AC source power (on the LV switchboard);

close the normal AC input circuit break- ers Q1 on the UPS units. The system powers up:

the rectifier/chargers automatically start, the green "rectifier/charger" lights 1 in the control panels go on,

lights 2 turn red;

close the battery circuit breakers QF1; lights 2 go off;

green lights 3 and 5 on the control panels go on;

close output switches Q5N for the inverters and in the external bypass unit;

open maintenance bypass switch Q3BP in the external bypass unit;

press the "inverter on" button 7 on each control panel:

the green "inverter" lights 4 flash;

when a sufficient number of inverters are ready, the inverter-output contactors close:

the green "inverter" lights 4 shine per- manently green;

the "static-bypass" lights 3 go off.

start-up of a module

start-up of a rectifier/charger

rectifier/charger start-up is automatic when the normal AC input circuit breaker

Q1 is closed:

the green "rectifier/charger" light 1 on the control panel goes on;

close battery circuit breaker QF1.

WARNING Rectifier/charger start-up is automatic when normal AC input circuit breaker Q1 is closed. DC voltage is present in the DC bus.

start-up of an inverter

When the rectifier/charger is on:

press the "inverter ON" button 7 on the control panel;

the green "inverter" light 4 flashes.

Single-UPS unit

the inverter starts, then, if the bypass AC source transfer conditions are satis- fied, the load is transferred to the inverter if the on-line mode is selected. For on- line mode:

the green "inverter" light 4 remains on, the "static-bypass" light 3 goes off.

Parallel UPS unit

 

Q1

Q4S

Q3BP

Q5N

 

Q1

Q5N

1

1

0

1

0

1

0

1

1

1

0

1

0

0

 

 

 

 

 

QF1

 

 

 

 

 

 

 

 

 

 

 

 

2

1

 

1

 

1

 

1

2

 

 

 

0

0

0

0

 

 

 

 

 

 

Q1

0

I

Q5N

 

 

 

 

 

 

 

 

3

1

 

1

 

1

 

1

3

1

0

1

 

0

0

0

 

0

0

 

 

 

 

 

 

 

 

 

QF1

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

1

 

0

I

 

 

 

 

 

 

 

5

 

1

 

1

 

1

 

 

 

 

0

0

0

0

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

4

 

 

 

the inverter starts and awaits the start of the other inverters;

when they are all on or enough have been started to supply the rated load power, the output switch for each running inverter closes and the load is supplied with power:

the green "static-bypass" light 3 goes off,

the green "inverter" light 4 on the con- trol panels of the running inverters goes on.

Fig. 15

Fig. 16

Start-up

13

Image 21
Contents Galaxy PW Page Galaxy PW User’s Manual Galaxy PW 100 to 225 kVA Important Safety Instructions This page intentionally left blank Service and Factory Repair Call 1 800 438 WarrantyGalaxy PW User’s Manual Galaxy PW TM 100 to 225 kVA User’s manualThis page intentionally left blank Contents Galaxy Pwtm 100 to 225 kVA How to use this manualIntroduction General characteristics of Galaxy PW UPSSystem description Schematic diagram of the Galaxy PW systemIsolation and protection devices Different types of Galaxy PW systemsSingle-UPS unit Parallel UPS system External bypass for parallel UPSs and the hot-swap optionBattery time Operation in on-line modeNormal operation Operation with the normal AC source downBattery charge cycle User’s Manual Operation with the normal AC source restoredInverter shutdown or overload Single-UPS unit on-line modeParallel UPSs with redundancy Parallel UPSs without redun- dancyOperation with an engine generator set Example of an installation with an engine generator setOutput voltage quality and continuity Steady state voltage regulationBattery cabinet Galaxy PW cabinetsUPS cabinet Control panel GeneralIndications Inverter on button Start-up System start-upStart-up of a module Shutdown of the inverter ShutdownControl-panel display Display of alarmsGeneral organization Display of messagesGalaxy Pwtm 100 to 225 kVA List of primary messages Load Protected ON-LINE ModeLoad on Mains User’s Manual List of secondary messagesBattery Charging BAT. = XXX a U BAT. = XXX Measurement system Voltage measurementsCurrent measurements Battery measurements Selections and settingsSet date and time Battery test Inverse videoPast events Maintenance bypass AlarmsSignal reception Signal transmissionEnvironment information Logging and time-stamping Presentation of event time-stamping by Galaxy PWUtilization via the Galaxy PW display Example Consulting statisticsNb of backups 1 min this is Elapsed backup time min this isMin nb of backups 3 min this is Total time with Tbatt 25 C h thisBattery Utilization via TeleserviceMaintenance configuration MaintenanceSingle-UPS unit UPS isolationIsolate all UPSs Galaxy PWGalaxy PW External bypass Battery maintenance Visual checkFunctional check Options Maintenance bypassGalvanic isolation and voltage matching transformers Electrical supervisionThis page intentionally left blank Scenic Avenue Costa Mesa, CA Reorder formPage Page Scenic Avenue, Costa Mesa, California 92626 714 557

Galaxy PW specifications

The MGE UPS Systems Galaxy PW is a high-performance uninterruptible power supply designed to provide reliable power protection for critical systems in various environments, including data centers, industrial settings, and commercial facilities. Known for its advanced features and innovative technologies, the Galaxy PW is engineered to ensure seamless operation, even in the event of power disturbances.

One of the standout features of the Galaxy PW is its modular design, allowing for easy scalability and flexibility. This design enables users to customize the power capacity according to their specific needs, accommodating future growth without requiring a complete system overhaul. The modular architecture consists of interchangeable power modules that can be easily added or replaced, ensuring minimal downtime and optimized performance.

The Galaxy PW uses cutting-edge double-conversion technology, which provides a high level of power quality and reliability. This technology ensures that any fluctuations in input power do not affect the output, delivering clean and stable electricity to connected equipment. This is particularly essential for sensitive electronics that require a consistent power supply to function correctly.

Another significant characteristic of the Galaxy PW is its energy efficiency. The UPS is designed to operate at high efficiency levels, often exceeding 96%. This not only helps in reducing the overall energy consumption but also lowers operational costs and reduces the carbon footprint of the facility. The Eco-Mode feature allows the UPS to deliver power with minimal energy loss during normal operating conditions.

The Galaxy PW is equipped with advanced communication and management features, including an intuitive graphical LCD display that provides real-time information on the system's status and performance metrics. Users can monitor input and output voltages, current load levels, and battery health at a glance. Additionally, the UPS supports various communication protocols and interfaces, facilitating integration with building management systems and remote monitoring tools.

Safety and reliability are also top priorities for the Galaxy PW. The system features robust battery management to extend the lifespan of the batteries while ensuring optimal performance. The UPS is designed with several protections, including overload, short-circuit, and thermal protection, to safeguard both the UPS and connected loads.

In summary, the MGE UPS Systems Galaxy PW integrates modularity, energy efficiency, advanced monitoring, and robust protection features to deliver unmatched reliability for critical power applications. Its innovative design and technologies make it an ideal choice for businesses seeking a reliable power protection solution.