MGE UPS Systems Comprehensive Guide to MGE Galaxy PW Power Supply Systems

Page 24

Galaxy PWTM 100 to 225 kVA

list of primary messages

LOAD PROTECTED

ON-LINE MODE

This is the normal display when there are no alarms or problems and the load is cor- rectly supplied by the inverter, in on-line mode.

LOAD PROTECTED

PARALLEL ON-LINE MODE

This is the normal display when there are no alarms or problems and the load is cor- rectly supplied by the inverter in a parallel UPS system, in on-line mode.

LOAD NOT PROTECTED

ON-LINE MODE

This display indicates that the load is not supplied by the inverter, or that there is no battery backup. The arrow indicates the presence of one or more problems specified in secondary messages.

The buzzer sounds continuously.

LOAD NOT PROTECTED

PARALLEL ON-LINE MODE

Situation identical to that in the previous screen, but for parallel UPS systems.

LOAD PROTECTED BATTERY DISCHARGING Remaining battery time (min) = XX % kW used = XXX

The load is supplied by the inverter, but the normal AC source is down or outside tolerances and power is supplied by the battery.

This message indicates the remaining bat- tery time in minutes prior to inverter shut- down and the percent load. The battery time calculation takes into account:

the percentage of full rated load power currently being drawn;

the type of battery;

battery temperature;

battery age.

The buzzer sounds slowly and discontinu- ously.

LOAD PROTECTED, LOW-BATTERY SHUTDOWN WARNING,

Remaining battery time (min) = XX % kW used = XXX

This message replaces the preceding if the power outage persists and the warning level has been reached.

The user is warned that the battery is about to shut down.

The buzzer sounds rapidly and discontinu- ously.

LOAD PROTECTED

ECO MODE

This is the normal display when there are no problems: the load is supplied by the inverter or the bypass AC source, and bat- tery backup is available.

LOAD NOT PROTECTED

ECO MODE

This display indicates that the load is sup- plied but has no battery backup. The arrow indicates the presence of one or more problems specified in secondary messages.

The buzzer sounds continuously.

LOAD FORCED TO INVERTER ECO MODE

The load has been transferred to the inverter following a specific request by the user.

16

Control-panel Display

Image 24
Contents Galaxy PW Page Galaxy PW User’s Manual Galaxy PW 100 to 225 kVA Important Safety Instructions This page intentionally left blank Warranty Service and Factory Repair Call 1 800 438Galaxy PW User’s Manual Galaxy PW TM 100 to 225 kVA User’s manualThis page intentionally left blank Contents How to use this manual Galaxy Pwtm 100 to 225 kVAGeneral characteristics of Galaxy PW UPS IntroductionSchematic diagram of the Galaxy PW system System descriptionDifferent types of Galaxy PW systems Isolation and protection devicesSingle-UPS unit Parallel UPS system External bypass for parallel UPSs and the hot-swap optionOperation in on-line mode Battery timeNormal operation Operation with the normal AC source downUser’s Manual Operation with the normal AC source restored Battery charge cycleSingle-UPS unit on-line mode Inverter shutdown or overloadParallel UPSs with redundancy Parallel UPSs without redun- dancyExample of an installation with an engine generator set Operation with an engine generator setOutput voltage quality and continuity Steady state voltage regulationBattery cabinet Galaxy PW cabinetsUPS cabinet Control panel GeneralIndications Inverter on button Start-up System start-up Start-up of a module Shutdown Shutdown of the inverterDisplay of alarms Control-panel displayGeneral organization Display of messagesLoad Protected ON-LINE Mode Galaxy Pwtm 100 to 225 kVA List of primary messagesUser’s Manual List of secondary messages Load on MainsBattery Charging BAT. = XXX a U BAT. = XXX Measurement system Voltage measurementsCurrent measurements Battery measurements Selections and settingsSet date and time Battery test Inverse videoPast events Alarms Maintenance bypassSignal reception Signal transmissionEnvironment information Logging and time-stamping Presentation of event time-stamping by Galaxy PWUtilization via the Galaxy PW display Consulting statistics ExampleElapsed backup time min this is Nb of backups 1 min this isMin nb of backups 3 min this is Total time with Tbatt 25 C h thisUtilization via Teleservice BatteryMaintenance Maintenance configurationSingle-UPS unit UPS isolationIsolate all UPSs Galaxy PWGalaxy PW External bypass Battery maintenance Visual checkFunctional check Maintenance bypass OptionsGalvanic isolation and voltage matching transformers Electrical supervisionThis page intentionally left blank Reorder form Scenic Avenue Costa Mesa, CAPage Page Scenic Avenue, Costa Mesa, California 92626 714 557