MGE UPS Systems Galaxy PW user manual Shutdown of the inverter

Page 22

Galaxy PWTM 100 to 225 kVA

shutdown

shutdown of the inverter

press the "inverter OFF" button 8 on the control panel for three seconds (see figure 19).

single-UPS unit

the green "inverter" light 4 on the con- trol panel goes off;

the green "static-bypass" light 3 goes on;

the inverter stops;

if bypass AC source (Mains 2) transfer conditions are satisfied, the inverter shuts down and the load is transferred to the bypass AC source;

if bypass AC source (Mains 2) transfer conditions are not satisfied, the inverter does not shut down. The message

"MAINS 2 OUTSIDE TOLERANCES, TRANSFER DISABLED" is displayed.

parallel UPS unit

if the system is redundant, i.e. the other parallel-connected inverters can supply the load on their own, the inverter shuts down and the green "inverter" light 4 goes off.

The load is not affected in that the other inverters continue to supply it normally;

if the system is not redundant, the other inverters go to overload status.

If overload conditions are overrun, the load is transferred to the bypass AC source:

the green lights 3 turn green,

the green "inverter" light 4 goes off.

shutdown of a rectifier/charger

It is recommended not to stop the rectifi- er/charger because the battery will no longer be charged. Except in the case of a test of the inverter on battery power, the rectifier/charger should be shutdown after the inverter to avoid unnecessary battery discharge.

Proceed in the following order:

open battery circuit breaker QF1;

open normal AC input circuit breaker Q1:

the rectifier/charger shuts down,

the green "rectifier/charger" light 1 goes off.

14

Shutdown

Image 22
Contents Galaxy PW Page Galaxy PW User’s Manual Galaxy PW 100 to 225 kVA Important Safety Instructions This page intentionally left blank Galaxy PW User’s Manual WarrantyService and Factory Repair Call 1 800 438 Galaxy PW TM 100 to 225 kVA User’s manualThis page intentionally left blank Contents How to use this manual Galaxy Pwtm 100 to 225 kVAGeneral characteristics of Galaxy PW UPS IntroductionSchematic diagram of the Galaxy PW system System descriptionSingle-UPS unit Parallel UPS system Different types of Galaxy PW systemsIsolation and protection devices External bypass for parallel UPSs and the hot-swap optionNormal operation Operation in on-line modeBattery time Operation with the normal AC source downUser’s Manual Operation with the normal AC source restored Battery charge cycleParallel UPSs with redundancy Single-UPS unit on-line modeInverter shutdown or overload Parallel UPSs without redun- dancyOutput voltage quality and continuity Example of an installation with an engine generator setOperation with an engine generator set Steady state voltage regulationGalaxy PW cabinets Battery cabinetUPS cabinet General Control panelIndications Inverter on button System start-up Start-upStart-up of a module Shutdown Shutdown of the inverterGeneral organization Display of alarmsControl-panel display Display of messagesLoad Protected ON-LINE Mode Galaxy Pwtm 100 to 225 kVA List of primary messagesUser’s Manual List of secondary messages Load on MainsBattery Charging BAT. = XXX a U BAT. = XXX Voltage measurements Measurement systemCurrent measurements Selections and settings Battery measurementsSet date and time Inverse video Battery testPast events Alarms Maintenance bypassSignal transmission Signal receptionEnvironment information Presentation of event time-stamping by Galaxy PW Logging and time-stampingUtilization via the Galaxy PW display Consulting statistics ExampleMin nb of backups 3 min this is Elapsed backup time min this isNb of backups 1 min this is Total time with Tbatt 25 C h thisUtilization via Teleservice BatterySingle-UPS unit MaintenanceMaintenance configuration UPS isolationGalaxy PW Isolate all UPSsGalaxy PW External bypass Visual check Battery maintenanceFunctional check Galvanic isolation and voltage matching transformers Maintenance bypassOptions Electrical supervisionThis page intentionally left blank Reorder form Scenic Avenue Costa Mesa, CAPage Page Scenic Avenue, Costa Mesa, California 92626 714 557

Galaxy PW specifications

The MGE UPS Systems Galaxy PW is a high-performance uninterruptible power supply designed to provide reliable power protection for critical systems in various environments, including data centers, industrial settings, and commercial facilities. Known for its advanced features and innovative technologies, the Galaxy PW is engineered to ensure seamless operation, even in the event of power disturbances.

One of the standout features of the Galaxy PW is its modular design, allowing for easy scalability and flexibility. This design enables users to customize the power capacity according to their specific needs, accommodating future growth without requiring a complete system overhaul. The modular architecture consists of interchangeable power modules that can be easily added or replaced, ensuring minimal downtime and optimized performance.

The Galaxy PW uses cutting-edge double-conversion technology, which provides a high level of power quality and reliability. This technology ensures that any fluctuations in input power do not affect the output, delivering clean and stable electricity to connected equipment. This is particularly essential for sensitive electronics that require a consistent power supply to function correctly.

Another significant characteristic of the Galaxy PW is its energy efficiency. The UPS is designed to operate at high efficiency levels, often exceeding 96%. This not only helps in reducing the overall energy consumption but also lowers operational costs and reduces the carbon footprint of the facility. The Eco-Mode feature allows the UPS to deliver power with minimal energy loss during normal operating conditions.

The Galaxy PW is equipped with advanced communication and management features, including an intuitive graphical LCD display that provides real-time information on the system's status and performance metrics. Users can monitor input and output voltages, current load levels, and battery health at a glance. Additionally, the UPS supports various communication protocols and interfaces, facilitating integration with building management systems and remote monitoring tools.

Safety and reliability are also top priorities for the Galaxy PW. The system features robust battery management to extend the lifespan of the batteries while ensuring optimal performance. The UPS is designed with several protections, including overload, short-circuit, and thermal protection, to safeguard both the UPS and connected loads.

In summary, the MGE UPS Systems Galaxy PW integrates modularity, energy efficiency, advanced monitoring, and robust protection features to deliver unmatched reliability for critical power applications. Its innovative design and technologies make it an ideal choice for businesses seeking a reliable power protection solution.