MGE UPS Systems Galaxy PW Maintenance configuration, Single-UPS unit, UPS isolation, Start-up

Page 36

Galaxy PWTM 100 to 225 kVA

maintenance

maintenance configuration

single-UPS unit

See figure 19. During maintenance, the UPS must be isolated from the normal and bypass AC source, the battery and the load.

UPS isolation

Proceed in the following order (see figure 20):

Q1

1

2

A

QF1

D

Q4S

B

Q5N

C

Q3BP

shut down the inverter (press the "invert-

er OFF" button 8 for three seconds),

close bypass switch Q3BP,

open isolating switches Q5N, Q4S, QF1

and Q1.

Fig. 19

The UPS is powered down once the

capacitors have discharged (a few min-

utes);

start-up

1

Q1

Q4S

Q3BP

Q5N

Q1 Q4S Q3BP Q5N

1

1

 

0

1

 

0

OFF

OFF

QF1

Following servicing, proceed in the follow-

ing order (see figure 21):

close switch Q1, then after approximate-

2

1

0

1

0

1

0

1

0

1

2

 

1

0

I

 

 

 

3

 

 

1

 

1

0

OFF

0

0

 

 

 

ly ten seconds, switches QF1, Q5N and

0

1

1

0

1

0

Q4S,

1

 

1

 

1

1

0

0

open bypass switch Q3BP,

start the inverter (press the "inverter ON"

button 7 ).

CAUTION

4

1

 

1

 

1

 

1

0

0

0

0

 

 

 

 

 

 

QF1

 

 

 

5

 

 

 

 

 

 

 

 

 

 

0

I

 

 

 

6

1

0

1

0

1

0

1

0

 

 

 

4

0

0

 

 

 

 

 

5

1

 

1

 

1

 

1

0

0

0

0

 

 

 

6

work should be car- ried out in accordance with applicable safety regulations;

to avoid interrupting the load, the various switching operations

must be carried out in the correct order. Operations are explained in dia- grams placed next to the switches;

the system cabinet is only partially powered down. The load is still supplied via the bypass AC source and switch Q3BP.

Fig. 20

Fig. 21

28

Maintenance

Image 36
Contents Galaxy PW Page Galaxy PW User’s Manual Galaxy PW 100 to 225 kVA Important Safety Instructions This page intentionally left blank Warranty Service and Factory Repair Call 1 800 438Galaxy PW User’s Manual Galaxy PW TM 100 to 225 kVA User’s manualThis page intentionally left blank Contents How to use this manual Galaxy Pwtm 100 to 225 kVAGeneral characteristics of Galaxy PW UPS IntroductionSchematic diagram of the Galaxy PW system System descriptionDifferent types of Galaxy PW systems Isolation and protection devicesSingle-UPS unit Parallel UPS system External bypass for parallel UPSs and the hot-swap optionOperation in on-line mode Battery timeNormal operation Operation with the normal AC source downUser’s Manual Operation with the normal AC source restored Battery charge cycleSingle-UPS unit on-line mode Inverter shutdown or overloadParallel UPSs with redundancy Parallel UPSs without redun- dancyExample of an installation with an engine generator set Operation with an engine generator setOutput voltage quality and continuity Steady state voltage regulationBattery cabinet Galaxy PW cabinetsUPS cabinet Control panel GeneralIndications Inverter on button Start-up System start-upStart-up of a module Shutdown Shutdown of the inverterDisplay of alarms Control-panel displayGeneral organization Display of messagesLoad Protected ON-LINE Mode Galaxy Pwtm 100 to 225 kVA List of primary messagesUser’s Manual List of secondary messages Load on MainsBattery Charging BAT. = XXX a U BAT. = XXX Measurement system Voltage measurementsCurrent measurements Battery measurements Selections and settingsSet date and time Battery test Inverse videoPast events Alarms Maintenance bypassSignal reception Signal transmissionEnvironment information Logging and time-stamping Presentation of event time-stamping by Galaxy PWUtilization via the Galaxy PW display Consulting statistics ExampleElapsed backup time min this is Nb of backups 1 min this isMin nb of backups 3 min this is Total time with Tbatt 25 C h thisUtilization via Teleservice BatteryMaintenance Maintenance configurationSingle-UPS unit UPS isolationIsolate all UPSs Galaxy PWGalaxy PW External bypass Battery maintenance Visual checkFunctional check Maintenance bypass OptionsGalvanic isolation and voltage matching transformers Electrical supervisionThis page intentionally left blank Reorder form Scenic Avenue Costa Mesa, CAPage Page Scenic Avenue, Costa Mesa, California 92626 714 557