American Power Conversion 10-40kW 208/480V manual Set input switches Q001 to position

Page 15

Stop/Start UPS and Operating the External Service Bypass

Action

Display shows

 

1.Check that the output switch (Q004) is set to position 0

2.Check that all output switches (Q002) are set to position 1

3. Set input switches (Q001) to position 1

**System OFF**

4.Wait 10 secs.

Open the UPS front door and

press the green ON button on all systems

Normal operation

load power 0%

 

 

5. Press

on the keyboard

 

6.

Press

or

on the keyboard until

7.

Press

on the keyboard

8.Press on the keyboard

All systems switch to bypass operation

Note!

If Q002s are in position 0 off, only programmed systems will switch to bypass

9.Set the output switch (Q004) to position 1

10.Turn the bypass switch (Q003) to position 0

The following can be carried out on any UPS

11. Press

on the keyboard

12. Press

or

on the keyboard until

13. Press

on the keyboard

14. Press

on the keyboard

All the systems will transfer to normal operation

Bypass operation

: NO

Bypass operation

: YES

Bypass operation

Lamp indication on Bypass Panel

H002 and H004 light up

Green light (H003) above bypass switch lights up

The green lamps (H002) and (H004) are switched off, but (H003) is lit until normal operation.

Display shows

Bypass operation

: YES

Bypass operation

: NO

Normal operation

load power 0%

No lamps on the bypass panel are lit

 

990-4034

 

 

User Guide APC Silcon 10-40kW 208V/480V UPS

15

Image 15
Contents Copyright 2000 APC Denmark ApS APC Silcon 10-40kW 208/480V UPS User GuideSafety Symbols used in this manual User Guide APC Silcon 10-40kW 208V/480V UPSThank You Contents Introduction IntroductionDisplay Unit Stop/Start UPS and Operating the External Service Bypass Stop UPS for stand-byStart UPS from stand-by Switching off the UPS Stop UPS for complete power downUPS start-up Start UPS from complete power downSystem start-up now completed Bypassing the Single System UPS Operating the External Service Bypass Switch single systemsUPS YES Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Operation OperationKeyboard Batt. load Batt. tank Display of Measured ValuesEconomy Mode Using the Remote DisplayParameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example Load power xx% Mode Comments Alarms and EventsAlarms and Events Displaying the Alarm StackDisplaying the Event Stack Possible AlarmsTemperature of main inverter, too Unlock Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Battery Capacity Test Maintenance & TestingMaintenance & Testing Battery Monitoring TestUntil Warranty WarrantyAPC Silcon UPS Limited Factory Warranty APC Denmark How to Contact APCHow to Contact APC APC Corporate