American Power Conversion 10-40kW 208/480V manual Using the Remote Display, Economy Mode

Page 19

Operation

3.3Using the Remote Display

The remote display is an inactive unit that is unable to influence the operation of the APC Silcon UPS. It is impossible to adjust or otherwise influence the function of the UPS. The alarms available on the remote display are at subset of the alarms, which can be read on the internal display.

Operation of Remote Display is described in section 3.0 above.

Alarms available are described in section 5.0 Alarms.

Readout of measurements as described in section 3.2 above.

NOTICE!

Time cannot be displayed from the Remote Display.

3.4Economy Mode

When the UPS is running in Economy Mode, the load will be supplied directly from utility and output voltages are UPS monitored. In the event of a utility disruption, the UPS will switch to battery mode without affecting the load.

Prior to switching to bypass mode, leave the system running in normal mode for 8-10 hours to charge batteries to full capacity.

To keep batteries fully charged, UPS is pre-programmed to switch back to normal operation whenever necessary.

Economy Mode not available for parallel configurations.

At start-up, the system will at first go into normal operation to ensure a fully charged battery, and it will then switch into bypass after the programmed time (8-10 hours).

NOTICE!

Check cable dimensions as input power factor is not corrected with UPS running in Economy Mode.

 

990-4034

 

 

User Guide APC Silcon 10-40kW 208V/480V UPS

19

Image 19
Contents Copyright 2000 APC Denmark ApS APC Silcon 10-40kW 208/480V UPS User GuideUser Guide APC Silcon 10-40kW 208V/480V UPS Safety Symbols used in this manualThank You Contents Introduction IntroductionDisplay Unit Stop UPS for stand-by Stop/Start UPS and Operating the External Service BypassStart UPS from stand-by Switching off the UPS Stop UPS for complete power downUPS start-up Start UPS from complete power downSystem start-up now completed Bypassing the Single System UPS Operating the External Service Bypass Switch single systemsUPS YES Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Operation OperationKeyboard Batt. load Batt. tank Display of Measured ValuesEconomy Mode Using the Remote DisplayParameter Settings Parameter SettingsParameter Settings Programming Keys Switching to Bypass OperationProgramming Example Load power xx% Mode Comments Alarms and EventsAlarms and Events Displaying the Alarm StackDisplaying the Event Stack Possible AlarmsTemperature of main inverter, too Unlock Parallel Operation Alarms Rectifying Alarm MessagesCorrection of false alarm situations during service Battery Capacity Test Maintenance & TestingMaintenance & Testing Battery Monitoring TestUntil Warranty WarrantyAPC Silcon UPS Limited Factory Warranty APC Denmark How to Contact APCHow to Contact APC APC Corporate