American Power Conversion 10-40kW 208/480V manual Bypassing the Single System UPS

Page 9

Stop/Start UPS and Operating the External Service Bypass

2.5Operating the External Service Bypass Switch (single systems)

2.5.1 Bypassing the Single System UPS

 

 

 

Utility

Load

 

 

 

 

 

 

 

Service Bypass

 

 

 

 

Switch

 

 

 

 

APC Silcon

 

 

 

 

UPS

 

Action

 

 

Display shows

1.

Press

on the keyboard

 

2.

Press

or

on the keyboard until

Bypass operation

: NO

 

 

 

 

3.

Press

on the keyboard

Bypass operation

: YES

 

 

 

 

4.

Press

on the keyboard

 

 

 

 

 

Lamp indication on

 

 

 

 

Bypass Panel

5.Check light indication on the bypass panel

6.Set the external bypass switch (Q003) to position 1

7.Set the output switch (Q002) to position 0

8.Open the front door and press the red OFF button

The acoustic alarm sounds for 30 seconds*

9.Set the input switch (Q001) to position 0

The red alarm LED below the display lights up and the acoustic alarm sounds for 30 seconds*

*Use the key to reset the acoustic alarm

Green light (H003) above the bypass switch handle (Q003) lights up

Green light (H002) above the output switch handle (Q002) lights up

Only the light (H002) above the output switch handle (Q002) is now on

Display shows

**System OFF**

 

990-4034

 

 

User Guide APC Silcon 10-40kW 208V/480V UPS

9

Image 9
Contents Copyright 2000 APC Denmark ApS APC Silcon 10-40kW 208/480V UPS User GuideSafety Symbols used in this manual User Guide APC Silcon 10-40kW 208V/480V UPSThank You Contents Introduction IntroductionDisplay Unit Stop/Start UPS and Operating the External Service Bypass Stop UPS for stand-byStart UPS from stand-by Switching off the UPS Stop UPS for complete power downUPS start-up Start UPS from complete power downSystem start-up now completed Bypassing the Single System UPS Operating the External Service Bypass Switch single systemsUPS YES Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Operation OperationKeyboard Batt. load Batt. tank Display of Measured ValuesEconomy Mode Using the Remote DisplayParameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example Load power xx% Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsDisplaying the Event Stack Possible AlarmsTemperature of main inverter, too Unlock Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil Warranty WarrantyAPC Silcon UPS Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC Denmark