Stop/Start UPS and Operating the External Service Bypass
2.7Isolating one UPS in a Parallel Configuration for Service/Maintenance
2.7.1 Isolating one UPS in a Parallel/Redundant System
Utility | Load |
Service bypass switch
APC Silcon
UPS
APC Silcon
UPS
In a redundant system one UPS may be isolated for service/maintenance without affecting other parallel UPS(s).
Action
1.Check that the remaining UPS(s) will be able to carry the load when one UPS is isolated.
2.Switch off the system to be isolated for maintenence by pushing the red OFF button.
3.Disconnect output and utility by setting output switches (Q002) to position 0 and input switch (Q001) to position 0. Disconnect battery by opening battery breaker.
2.7.2Switching Back the UPS to Normal Rarallel/Redundant Operation
Action
1.Set the input switch (Q001) and the output switch (Q002) to position 1.
2.Charge capacitors, connect battery, and start up the UPS as described in 2.4.1. Start UPS (from complete power down).
The UPS will automatically switch to normal operation and start
WARNING!
The system will discharge
ALWAYS check with a multimeter that the terminals contain no dangerous voltage before touching the system!
NOTICE!
With Q002 in position 0, the UPS can be operated and tested as a single system without affecting the other parallel UPS(s) if correct monitoring device has been installed. Applicable to all bypass panels.
16 | User Guide APC Silcon |