Alarms and Events
34. | Output outside tolerance | Output voltage outside tolerance | Call for assistance |
|
|
|
|
35. | Output frequency outside | Output frequency outside | Call for assistance |
| tolerance | tolerance |
|
|
|
|
|
36. | High battery temperature | Battery ambient temperature too | Check system ambient |
|
| high | temperature, check fan, check for |
|
|
| airflow obstructions |
|
|
|
|
37. | Battery weak | Battery capacity below 75% or | Test battery capacity |
|
| battery MCCB/fuse switched off |
|
|
|
|
|
38. | Battery defective | Insufficient battery capacity or | Call for assistance |
|
| battery MCCB/fuse switched off |
|
|
|
|
|
39. | System locked in operation | UPS has made 10 attempts within | Unlock. |
| mode | 1 minute to switch from bypass to | If message reappears - |
|
| battery operation, or “High DC | call for assistance |
|
| warning” has appeared |
|
|
| times within 1 minute |
|
|
|
|
|
40. | RAM1 memory write error | UPS fault | Call for assistance |
|
|
|
|
41. | Memory write error | UPS fault | Call for assistance |
|
|
| |
42. Communication to VQ bypass | UPS fault | Call for assistance | |
| lost |
|
|
|
|
| |
43. Communication to VQ output | UPS fault | Call for assistance | |
| lost |
|
|
|
|
|
|
44. | Communication to DMU lost | UPS fault | Call for assistance |
|
|
|
|
45. | Communication to controller | UPS fault. | Call for assistance |
| lost | Display will show invalid UPS |
|
|
| data |
|
|
|
|
|
46. | Communication to parallel IF | UPS fault | Call for assistance |
| lost |
|
|
|
|
|
|
47. | External shutdown accepted | Remote signal for switching off | – |
|
| UPS accepted. |
|
|
| UPS switches off automatically |
|
|
|
|
|
48. | Communication to VQ mains | UPS fault | Call for assistance |
| lost |
|
|
|
|
|
|
49. | Bypass syncronization error | The UPS cannot synchronize with | Check if phase rotation of bypass |
|
| bypass mains | voltage is correct – if OK, call for |
|
|
| assistance |
|
|
|
|
50. | Battery charge error | Transferred to battery operation | Check RFI input fuse and |
|
| because of battery charge error | feedback relay |
|
|
|
|
26 | User Guide APC Silcon |