Page 26

Alarms and Events

34.

Output outside tolerance

Output voltage outside tolerance

Call for assistance

 

 

 

 

35.

Output frequency outside

Output frequency outside

Call for assistance

 

tolerance

tolerance

 

 

 

 

 

36.

High battery temperature

Battery ambient temperature too

Check system ambient

 

 

high

temperature, check fan, check for

 

 

 

airflow obstructions

 

 

 

 

37.

Battery weak

Battery capacity below 75% or

Test battery capacity

 

 

battery MCCB/fuse switched off

 

 

 

 

 

38.

Battery defective

Insufficient battery capacity or

Call for assistance

 

 

battery MCCB/fuse switched off

 

 

 

 

 

39.

System locked in operation

UPS has made 10 attempts within

Unlock.

 

mode

1 minute to switch from bypass to

If message reappears -

 

 

battery operation, or “High DC

call for assistance

 

 

warning” has appeared 10-20

 

 

 

times within 1 minute

 

 

 

 

 

40.

RAM1 memory write error

UPS fault

Call for assistance

 

 

 

 

41.

Memory write error

UPS fault

Call for assistance

 

 

 

42. Communication to VQ bypass

UPS fault

Call for assistance

 

lost

 

 

 

 

 

43. Communication to VQ output

UPS fault

Call for assistance

 

lost

 

 

 

 

 

 

44.

Communication to DMU lost

UPS fault

Call for assistance

 

 

 

 

45.

Communication to controller

UPS fault.

Call for assistance

 

lost

Display will show invalid UPS

 

 

 

data

 

 

 

 

 

46.

Communication to parallel IF

UPS fault

Call for assistance

 

lost

 

 

 

 

 

 

47.

External shutdown accepted

Remote signal for switching off

 

 

UPS accepted.

 

 

 

UPS switches off automatically

 

 

 

 

 

48.

Communication to VQ mains

UPS fault

Call for assistance

 

lost

 

 

 

 

 

 

49.

Bypass syncronization error

The UPS cannot synchronize with

Check if phase rotation of bypass

 

 

bypass mains

voltage is correct – if OK, call for

 

 

 

assistance

 

 

 

 

50.

Battery charge error

Transferred to battery operation

Check RFI input fuse and

 

 

because of battery charge error

feedback relay

 

 

 

 

990-4034

26

User Guide APC Silcon 10-40kW 208V/480V UPS

Image 26
Contents APC Silcon 10-40kW 208/480V UPS User Guide Copyright 2000 APC Denmark ApSThank You Safety Symbols used in this manualUser Guide APC Silcon 10-40kW 208V/480V UPS Contents Display Unit IntroductionIntroduction Start UPS from stand-by Stop/Start UPS and Operating the External Service BypassStop UPS for stand-by Stop UPS for complete power down Switching off the UPSStart UPS from complete power down UPS start-upSystem start-up now completed Operating the External Service Bypass Switch single systems Bypassing the Single System UPSUPS YES Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Keyboard OperationOperation Display of Measured Values Batt. load Batt. tankUsing the Remote Display Economy ModeParameter Settings Parameter SettingsParameter Settings Programming Example Switching to Bypass OperationProgramming Keys Load power xx% Displaying the Alarm Stack Alarms and EventsAlarms and Events Mode CommentsPossible Alarms Displaying the Event StackTemperature of main inverter, too Unlock Correction of false alarm situations during service Rectifying Alarm MessagesParallel Operation Alarms Battery Monitoring Test Maintenance & TestingMaintenance & Testing Battery Capacity TestUntil APC Silcon UPS Limited Factory Warranty WarrantyWarranty APC Corporate How to Contact APCHow to Contact APC APC Denmark