Parameter Settings
4.0 Parameter Settings
Below tables show operating parameters programmable from keyboard. Only qualified users should alter programming parameters. See below examples.
Parameter Settings
Parameter | Setting* |
| Comments |
| |||
|
|
|
|
|
| ||
Bypass operation | YES, NO | YES will switch the system into | |||||
|
| bypass mode*** |
| ||||
|
|
|
|
|
| ||
Language | GB, D, F, DK, S, SF, NL, PL, CZ, | Languages of text in display | |||||
| E, P, SK, H |
|
|
|
|
|
|
|
|
|
|
|
| ||
Autostart | YES, NO | Automatic restart by utility return | |||||
|
| (1 min. delay). Ensures quick | |||||
|
| battery recharge. |
| ||||
|
|
|
|
|
| ||
Remote shutdown active | YES, NO | Shutdown of UPS by remote | |||||
|
| signal when in battery operation. | |||||
|
| Saves battery energy. |
| ||||
|
|
|
|
|
| ||
Remote shutdown | HIGH, LOW | Nature of remote shutdown | |||||
|
| signal level |
|
|
| ||
|
|
|
|
|
| ||
Remote shutdown time | 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 min. | Time delay on remote shutdown | |||||
|
| of UPS |
|
|
| ||
|
|
|
|
|
| ||
Battery capacity test | – | Initiates | |||||
|
| Time measured from start until it | |||||
|
| reaches low DC warning level | |||||
|
| (See User Guide, section 6). | |||||
|
|
|
|
|
| ||
Battery monitor test ** | – | Initiates checks of battery | |||||
|
| condition by 25% discharging. | |||||
|
|
|
|
|
| ||
Automatic battery test** | OFF, 3,6 months | Activates the battery monitor test | |||||
|
| in cyclic intervals. |
| ||||
|
|
|
|
|
|
|
|
Battery monitor reset** | – | Press the |
|
| and |
| key to |
|
| reset alarm |
|
|
|
|
|
|
|
|
|
|
| ||
|
| (flashing light). |
|
|
| ||
|
|
|
|
|
| ||
Boost charge | YES, NO | YES results in boost charge (10 | |||||
|
| hours) |
|
|
| ||
|
|
|
|
|
| ||
Autoboost charge | YES, NO | YES results in boost charge after | |||||
|
| battery operation (10 hours). | |||||
|
|
|
|
|
|
| |
Enter new date | YYMMDD | Set to local date |
| ||||
|
|
|
|
|
| ||
Enter new time | HHMMSS | Set to local time (24 hour clock) | |||||
|
|
|
|
|
|
|
|
*Factory settings in bold
**For systems with active Battery Monitor only
***Do not leave system running in bypass mode (Static bypass) for extended periods of time, as batteries are not recharged in bypass mode.
20 | User Guide APC Silcon |