American Power Conversion 10-40kW 208/480V manual Parameter Settings

Page 20

Parameter Settings

4.0 Parameter Settings

Below tables show operating parameters programmable from keyboard. Only qualified users should alter programming parameters. See below examples.

Parameter Settings

Parameter

Setting*

 

Comments

 

 

 

 

 

 

 

Bypass operation

YES, NO

YES will switch the system into

 

 

bypass mode***

 

 

 

 

 

 

 

Language

GB, D, F, DK, S, SF, NL, PL, CZ,

Languages of text in display

 

E, P, SK, H

 

 

 

 

 

 

 

 

 

 

 

 

Autostart

YES, NO

Automatic restart by utility return

 

 

(1 min. delay). Ensures quick

 

 

battery recharge.

 

 

 

 

 

 

 

Remote shutdown active

YES, NO

Shutdown of UPS by remote

 

 

signal when in battery operation.

 

 

Saves battery energy.

 

 

 

 

 

 

 

Remote shutdown

HIGH, LOW

Nature of remote shutdown

 

 

signal level

 

 

 

 

 

 

 

 

 

Remote shutdown time

0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 min.

Time delay on remote shutdown

 

 

of UPS

 

 

 

 

 

 

 

 

 

Battery capacity test

Initiates back-up time check.

 

 

Time measured from start until it

 

 

reaches low DC warning level

 

 

(See User Guide, section 6).

 

 

 

 

 

 

Battery monitor test **

Initiates checks of battery

 

 

condition by 25% discharging.

 

 

 

 

 

 

Automatic battery test**

OFF, 3,6 months

Activates the battery monitor test

 

 

in cyclic intervals.

 

 

 

 

 

 

 

 

 

Battery monitor reset**

Press the

 

 

and

 

key to

 

 

reset alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

(flashing light).

 

 

 

 

 

 

 

 

 

Boost charge

YES, NO

YES results in boost charge (10

 

 

hours)

 

 

 

 

 

 

 

 

 

Autoboost charge

YES, NO

YES results in boost charge after

 

 

battery operation (10 hours).

 

 

 

 

 

 

 

Enter new date

YYMMDD

Set to local date

 

 

 

 

 

 

 

Enter new time

HHMMSS

Set to local time (24 hour clock)

 

 

 

 

 

 

 

 

*Factory settings in bold

**For systems with active Battery Monitor only

***Do not leave system running in bypass mode (Static bypass) for extended periods of time, as batteries are not recharged in bypass mode.

990-4034

20

User Guide APC Silcon 10-40kW 208V/480V UPS

Image 20
Contents APC Silcon 10-40kW 208/480V UPS User Guide Copyright 2000 APC Denmark ApSThank You Safety Symbols used in this manualUser Guide APC Silcon 10-40kW 208V/480V UPS Contents Display Unit IntroductionIntroduction Start UPS from stand-by Stop/Start UPS and Operating the External Service BypassStop UPS for stand-by Stop UPS for complete power down Switching off the UPSStart UPS from complete power down UPS start-upSystem start-up now completed Operating the External Service Bypass Switch single systems Bypassing the Single System UPSUPS YES Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Keyboard OperationOperation Display of Measured Values Batt. load Batt. tankUsing the Remote Display Economy ModeParameter Settings Parameter SettingsParameter Settings Programming Example Switching to Bypass OperationProgramming Keys Load power xx% Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsPossible Alarms Displaying the Event StackTemperature of main inverter, too Unlock Correction of false alarm situations during service Rectifying Alarm MessagesParallel Operation Alarms Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil APC Silcon UPS Limited Factory Warranty WarrantyWarranty How to Contact APC How to Contact APCAPC Corporate APC Denmark