American Power Conversion VT ISX manual Operation Procedures

Page 21

Operation Procedures

Turn into mechanical bypass using the Mechanical Bypass Lever

The load is not protected by the UPS when the internal mechanical bypass system is active, and, the power is not conditioned.

Caution

If the UPS is running and controllable through the display, carry out steps 1 through 5. If not, go directly to step 4.

Note

Control

Display

Status

Diags

Setup

Help

Logging

 

Main Menu

From the Main Menu, select Control and press ENTER

Use UP/DOWN key to navigate to UPS into Bypass and press ENTER

Use UP/DOWN key to navigate to YES, confirm UPS into bypass, and press ENTER

Remove UPS Front Panel

!

Output

Pwr

Zone

 

 

 

 

Probe

10/100Base-T

 

Reset

 

 

 

 

 

 

10/100

 

 

AP9619

Network Management Card EM

 

 

 

 

 

 

 

 

 

 

 

BATTERY UNIT

 

 

 

 

BATTERY UNIT

 

 

 

 

BATTERY UNIT

 

 

 

 

BATTERY UNIT

Turn the Mechanical Bypass Lever upwards to activate the internal mechanical bypass switch. The load will now be supported directly by mains power.

990-2820A

Smart-UPS® ISX 30-40 kVA, 400V Operation

15

Image 21
Contents Operation Page How to find updates to this manual About this ManualCompanion manuals Page Contents Configuration Safety System Overview OverviewOpening front and rear doors System ComponentsUser interface front User interface area rear Battery ModuleRear cover of this manual DisplayOverview The Display Menu treeControl functions Basic display navigation principlesStatus views Select YES, Turn Load onLogging Clock set-upSelect View Statistics Display setup Alarm thresholdDiagnostics screen Vol VolumeOperation Modes OperationOperation Procedures Turn into normal operation from mechanical bypass operation Connecting load to the PDUs ConfigurationConnecting 1-phase load to PDU Connection of Load to the PDUConnecting 3-phase load to PDU PDU output breaker ratings Disconnecting load from the PDUsParts Replacement How to determine if you need a replacement partHow to return parts to APC How to remove Battery Modules How to install a Battery Module How to replace a Network Management Card Display messages TroubleshootingTroubleshooting Parts Replacement Troubleshooting Parts Replacement Restart Power applicationVoltage confirmation Page APC Worldwide Customer Support 990-2820A05/2006