American Power Conversion VT ISX manual Basic display navigation principles, Control functions

Page 14

Overview – The Display

Basic display navigation principles

All illustrated display screens are examples only!

Note

On the display, press ESC until you get to the Overview Screen, which provides you with basic system status information.

Press UP, DOWN arrows to navigate with the selector arrow and view all sub-menu screens.

Chrg 100% Load 000% 230Vin 000Vout 50Hz Runtime: 0hr 0m

Overview Screen

Press ENTER to open the Main Menu screen. From here, you command, configure, and monitor the system.

Control

Logging

Status

Display

Setup

Diags

 

Help

Main Menu

Control functions

From the Control Screen on the Main Menu, you can select the following functions:

1.Turn Load OFF/ON

2.Switch the UPS into Bypass/out of Bypass

Warning

Control

Logging

Status

Display

Setup

Diags

 

Help

Main Menu

Disconnecting the UPS output to the load does NOT de-energize the UPS! Always follow the Total-Power-OFFprocedure if you need to de-energize the UPS in emergency situations!

Switch load OFF (disconnect the UPS output to the load equipment).

1.From the Main Menu, select Control and press ENTER

2.Use UP/DOWN key to navigate to Turn Load OFF, and press ENTER

3.Select YES, Turn Load OFF

8

Smart-UPS® ISX 30-40 kVA, 400V Operation

990-2820A

Image 14
Contents Operation Page Companion manuals How to find updates to this manualAbout this Manual Page Contents Configuration Safety Overview System OverviewSystem Components Opening front and rear doorsUser interface front Battery Module User interface area rearDisplay Rear cover of this manualMenu tree Overview The DisplayBasic display navigation principles Control functionsSelect YES, Turn Load on Status viewsClock set-up LoggingSelect View Statistics Alarm threshold Display setupVol Volume Diagnostics screenOperation Operation ModesOperation Procedures Turn into normal operation from mechanical bypass operation Connecting 1-phase load to PDU ConfigurationConnecting load to the PDUs Connection of Load to the PDUConnecting 3-phase load to PDU Disconnecting load from the PDUs PDU output breaker ratingsHow to return parts to APC Parts ReplacementHow to determine if you need a replacement part How to remove Battery Modules How to install a Battery Module How to replace a Network Management Card Troubleshooting Display messagesTroubleshooting Parts Replacement Troubleshooting Parts Replacement Power application RestartVoltage confirmation Page 05/2006 APC Worldwide Customer Support990-2820A