American Power Conversion AP7922 quick start How to Download Firmware Updates, Xmodem

Page 21

How to Download Firmware Updates

For a complete description on how to download a firmware upgrade for your Rack PDU, see the Addendum on the

See also provided APC Switched Rack PDU Utility CD.

You can use a local computer that connects to the Rack PDU through the serial port on the front of the unit.

1. Select a serial port at the local computer, and disable any service that uses that port.

2.Use the configuration cable (940-0144) to connect the selected port to the RJ-12 serial port on the front panel of the Rack PDU.

3.Run a terminal program (such as HyperTerminal) and configure the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control. Save the changes.

4.Press ENTER twice to display the User Name prompt.

5.Enter your user name and password (both apc, for administrators only) and press ENTER.

6.From the Control Console menu, select System, then Tools, then

XMODEM.

7.The system will prompt you with Perform transfer with XMODEM -CRC? Type Yes and press ENTER.

8.The system will then prompt you to choose a transfer rate and to change your terminal settings to match the transfer rate. Press ENTER to set the Rack PDU to accept the download.

9.In the terminal program, send the file using the XMODEM protocol. Upon completion of the transfer, the console will prompt you to restore the baud rate to normal.

Do not interrupt the download.

Caution

The Rack PDU will reboot when the download is complete.

Upgrading the firmware will not interfere with the operation of the outlets.

Note

Switched Rack PDU Installation and Quick Start

17

Image 21
Contents Switched Rack Power Distribution Unit Page Contents Specifications AP7922 Product Description and InventoryDocumentation AdditionalInventory Receiving inspectionHow to Install the Rack PDU Mounting options How to Install the Rack PDU Display interface OperationQuick Configuration TCP/IP configuration methodsOverview Bootp the default setting ConfigurationQuick Configuration Option 43 = 01 04 31 41 50 43 where Local access to Remote access toControl console Use apc for both user name and password Use Telnet to access the Rack PDU at its newly assigned IPControl console on page 11 or Remote access to the control If you are not using a Bootp or Dhcp server to configureWeb interface Telnet/SSH If you enable SSL and SSH, disable FTP. Allowing file Transfers using FTP compromises the high securityEnvironment of SSL and SSH. Administrators can disable How to Recover From a Lost Password Xmodem How to Download Firmware UpdatesElectrical SpecificationsLimited warranty Warranty and ServiceWarranty limitations Obtaining serviceGeneral policy Life-Support PolicyExamples of life-support DevicesResponsibility for correcting such interference Radio Frequency InterferenceCanada-ICES Japan-VCCIAPC Worldwide Customer Support