5.6.LVD Operation

In order to prevent damage to the battery due to deep discharge, the dc power system has a Low Voltage Disconnect (LVD). When the battery voltage reaches the threshold set by the LVD 1 Trip Voltage setting during discharge, the dc power system will activate the LVD contactor to disconnect the battery from the system. The LVD will remain open until ac power is restored to the system and the bus voltage reaches the level defined by the LVD 1 Reset Voltage variable. The LVD control can be disabled on the LVD parameters screen in the controller.

The LVD will not be energized until a battery string is installed with the correct polarity and the battery disconnect switch is turned on. This will prevent the battery from being hooked up backwards and damaging the rectifiers and/or the loads. Once the battery is connected correctly and the LVD is closed, the LVD will open only in low voltage situations. The battery connections are to be used for the battery only.

5.7.Programming Output Relays

Any alarm condition such as System High Voltage Alarm, Battery Discharge Alarm, or Rectifier 1 of n Alarm can be programmed to any of the eight output relays. Programming alarms to the output relays 1-6 will give a much better idea of what the failure is before actually visiting the site. Using the default programming, over twenty conditions could cause activate a minor relay. However, if you program Battery Discharge Alarm to Output Relay 1, you will know exactly what the alarm is just by knowing that output relay 1 is on. The network management card also displays the output relays individually and can be set up to e-mail these messages.

Output relay mapping options are Ignore, Major, Minor, and Output Relay 1-6. To program the alarm to an output relay find the alarm setup screen for the desired alarm from the table in Figure 5.5-1. The Ignore setting will not send an alarm to any display or relay. Programming the alarm to Major, Minor or Output Relay 1 will send the alarm to the relay output connector on the back of the plant, turn on the appropriate front panel LED, and will send the alarm to the network management card. Programming the alarm to Output Relay 2-6 will not send the alarm to the relay output connector on the back of the plant, but will turn on the front panel Out Relay LED, and will send the alarm to the network management card. For instance, go to the Batteries / Parameters screen and program Battery Discharge Alarm to Output Relay 1. When the battery discharge current goes above the default setting of 5 Amps, the alarm will come on, the Out Relay contact will energize, the front panel Out Relay LED will come on and the network management card will report Output Relay 1 is on.

Most alarms are originally assigned to a minor or major relay. Usually it is desirable to keep the minor and major assignments when programming to the output relays. To do this, go to the output relay-programming screen and map the relay back to the desired minor or major relay. For instance, go to the I/O / Output screen and program Relay 1 to Minor Relay. When the battery discharge current goes above the default setting of 5 Amps, the alarm will come on, the Out Relay contact will energize, the Out Relay LED will come on, and the network management card will report Output Relay 1 is on. In addition, the Minor Relay contact will energize, the front panel Minor LED will come on, and the network management card will report the Minor Relay is on. With this scheme of programming, you will know that you have a minor alarm and specifically that the batteries are discharging.

Out Relay 1-6 can be renamed using the Relay Alias setup screen. Each relay name can be up to sixteen characters in length. This name will not appear in the alarm summary, but will appear in the messages generated by the network management card. This can be used to give specific information on the exact nature of the active alarm. Using the example above, if you use the default programming, the message “A minor relay in the power plant has been activated.” will be reported. Using the relay mapping and aliasing you could get the additional message “An output relay (1; Batt Discharge) for the power plant has been activated.”

Magnum VS –48 Vdc User Manual

Page 41

Image 41
Contents Magnum VS Vdc Power Systems Table of Contents Programming Output Relays Table of Figures Page General Information IntroductionDescription AccessoriesControl Power Distribution BackplaneUnpacking Equipment InstallationMechanical Installation AC Connections AC Power ConnectionsAC Power Cord Sets Planning the Battery installation Battery ConnectionsConnecting the Cables Recommended toCounter Electro-Motive Force Cemf Cell Connections Battery Temperature Probe Installation1 Cemf Connection Locations DC System GroundingCircuit Breaker Installation Load Protection InstallationGMT Fuse Installation Load ConnectionsGMT Fuse-protected Load Connections Circuit Breaker Protected Load Connections 30 or 60 aMonitoring and Relay Output Connections RJ45 Ethernet ConnectorFront Panel DB9 Connection Major, Minor and Relay 1 Output Connections1 Interface Connections Output Relay 2-6 Connections2 Output Relay Connections External Alarm Input ConnectionsController Module Installation Rectifier Module InstallationBattery Visual and Safety Inspection Electrical InstallationCommissioning Pre-Commissioning InspectionDC Power Up AC Power UpCommissioning Initial Set-upRectifier Test Battery Power UpLVD Test Circuit Breaker/ Fuse TestOutput Relay Battery Temperature CompensationFinal Inspection System Management Technical DescriptionRectifier Management Load Management System Status and Alarm ReportingSystem Current Monitor Circuit BreakersGMT Fuses Battery ManagementBattery Charging Battery Temperature Monitoring Battery ProtectionBattery Low Voltage Disconnect Counter Electro-Motive Force Module ConnectionsAlarm Outputs Output Relays Controls and IndicatorsExternal Alarm Inputs User Input Network Management Card Local & Remote MonitoringController Module Jumpers OperationDescription 1 Controller Card Jumper Locations Controller ModuleMagnum VS Controller Operation Using the RS-232 Comm PortOperation Using the 10/100 BaseT Ethernet Port Settings in Bold Settings DefaultDistribution/Breakers 00 mVSystem/Date & Time Power Modules/RectifiersDistribution/Fuses Batteries ParametersSeconds Input Output DisableSeconds, 0.00 seconds Output RelaySystem/Out-Rly/Alias System/Preferences Programming Output Relays LVD OperationSystem Visual and Safety Inspection Preventive MaintenanceEquipment InspectionTest Battery Preventive Maintenance Procedure Battery Current TestBattery Temperature Test Final Inspection Alarm Summary System LT Alm System Temperature is below Minor Magnum VS 50 Power System SpecificationsMagnum VS 100 Power System AC InputDC Output Magnum VS Controller Environmental MechanicalCompliance APC Worldwide Customer Support Warranty Claims Terms of WarrantyNon-transferable Warranty Exclusions