Storage, Maintenance, Transport, and Service

Storage, Maintenance, Transport, and Service

Storage

Store the UPS covered in a cool, dry location with the battery(s) fully charged.

At 5° to 113° F (–15° to 45° C), charge the UPS battery every six months.

To Install a Replacement Battery

This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, iso- lated from electrical hazards. You may leave the UPS and connected equipment on during the replacement procedure.

Once the batteries are disconnected, the connected equipment is not protected from power outages.

Caution

Refer to the appropriate replacement battery user manual for battery module installation instructions. See your dealer or contact APC at www.apc.com for information on replacement battery modules.

Be sure to deliver the spent battery(s) to a recycling facility or ship it to APC in the replacement battery packing material.

Transporting the UPS to Another Location

Perform these steps before transporting the UPS to another location.

1.Shut down and disconnect any equipment attached to the UPS.

2.Shut down and disconnect the UPS from the utility or power supply.

3.Disconnect the battery.

a.Remove the front bezel .

b.Remove the battery cover .

c.Unsnap the battery connectors .

4.Place a protective sticker or packaging between the battery connectors to ensure that the connectors do not become re-engaged during transport.

5.Reinstall the battery cover .

10 Smart-UPS RT SURTA1500XL/SURTA1500XLJ/SURTA2000XL Uninterruptible Power Supply User Manual

Image 10
Contents Unpacking and Equipment Placement Introduction/Before InstallationContact Information Safety Information About this ManualTo Install the UPS as a Tower Configuration InstallationTo Install the UPS in a Rack To Install the UPS with External Battery PacksConnectors Type Description If Required, Connect the Emergency Power Off EPO Feature  Connect the Battery and Install the Front Bezel Connect Power and Start Up the UPS Terminal Mode ConfigurationFor Additional Computer System Security Operation Display Panel IndicatorsDisplay Panel On Battery Operation LEDConfiguration Settings Utility Voltage MeasurementFunction Factory Default User Selectable Description Choices Storage Storage, Maintenance, Transport, and ServiceTo Install a Replacement Battery Transporting the UPS to Another LocationBattery Replacement Instructions ServiceTroubleshooting Problem and/or Possible Cause SolutionEquipment There is no utility power Radio Frequency Warning Regulatory ApprovalsCopyright Notice Limited Warranty990-1856A 06/2004