Operation
b. Select the COM port that is connected to the UPS. The port settings are:
•Bits per second - 2400
•data - bits 8
•parity - none
•stop bit - 1
•flow control - none
c.Press Enter.
4.Once the terminal window is open, follow these steps to set the number of external battery packs (SURTA48XLBP or SURTA48XLBPJ):
a.Press Enter to initiate terminal mode. Follow the prompts.
b.Press 1 to modify UPS settings. Press e (or E) to modify the number of battery packs.
c.Enter the number of battery packs, including the internal battery module (Number of packs: 1 = internal battery module, 2 = one SURTA48XLBP or SURTA48XLBPJ, 3 = two SURTA48XLBP or SURTA48XLBPJ, etc.)
d.Press Enter.
e.Follow the prompts.
5.Exit the terminal program.
Operation
Display Panel
Load | Battery Charge |
Percentages | Percentages |
85% | 96% |
68% | 72% |
51% | 48% |
34% | 24% |
17% | 0% |
Display Panel Indicators
Indicator | Indicator Title | Description | |
LED | |||
|
| ||
|
|
| |
| On Line | The UPS is supplying utility power to the connected equipment. |
On Battery
The UPS is supplying battery power to the connected equipment.
6