| Configuration Settings | |
|
|
|
| ||
Function | Factory Default | User Selectable | Description | ||
Choices | |||||
|
|
| |||
|
|
|
|
| |
Low Battery | 2 minutes | • 2 m | • 14 m | PowerChute software interface provides auto- | |
Warning |
| • 5 m | • 17 m | matic, unattended shutdown when approxi- | |
|
| • 8 m | • 20 m | mately two minutes of battery operated run | |
|
| time remains. | |||
|
| • 11 m | • 23 m | ||
|
| The | |||
|
|
|
| ||
|
|
|
| when two minutes of run time remain. | |
|
|
|
| Change the low battery warning interval set- | |
|
|
|
| ting to the time that the operating system or | |
|
|
|
| system software requires to safely shut down. | |
|
|
|
|
| |
Synchronized | 0 seconds | • 0 s | • 240 s | Specify the time the UPS will wait after the | |
| • 60 s | • 300 s | return of utility power before start up (to avoid | ||
|
| • 120 s | • 360 s | branch circuit overload). | |
|
| • 180 s | • 420 s |
| |
|
|
|
|
| |
High Bypass Points | 100V Models: | 100V | 120V | Maximum voltage that the UPS will pass to | |
| 110V | • 107V | • 127V | connected equipment during internal bypass | |
| 120V Models: | • 110V | • 130V | operation. | |
| 133V | • 113V | • 133V |
| |
|
| • 116V | • 136V |
| |
|
| • 119V | • 139V |
| |
|
| • 122V | • 142V |
| |
|
| • 125V | • 145V |
| |
|
| • 128V | • 148V |
| |
|
|
|
|
| |
Low Bypass Points | 100V Models: | 100V | 120V | Minimum voltage that the UPS will pass to | |
| 78V | • 78V | • 86V | connected equipment during internal bypass | |
| 120V Models: | • 80V | • 88V | operation. | |
| 86V | • 82V | • 90V |
| |
|
| • 84V | • 92V |
| |
|
| • 86V | • 94V |
| |
|
| • 88V | • 96V |
| |
|
| • 90V | • 98V |
| |
|
| • 92V | • 100V |
| |
|
|
|
|
| |
Output Frequency | Automatic | 50 ± 3 Hz or |
| Sets the allowable UPS output frequency. | |
| 50 ± 3 Hz or | 50 ± 0.1 Hz |
| Whenever possible, the output frequency | |
| 60 ± 3 Hz | 60 ± 3 Hz or |
| tracks the input frequency. | |
|
|
| |||
|
| 60 ± 0.1 Hz |
|
| |
|
|
|
| ||
Number of Battery | 1 | Number of connected bat- | Defines the number of connected battery packs | ||
Packs |
| tery packs |
| for proper run time prediction. | |
|
|
|
| 1 = internal battery module, | |
|
|
|
| 2 = one SURTA48XLBP or SURTA48XLBPJ, | |
|
|
|
| 3 = two SURTA48XLBP or SURTA48XLBPJ, | |
|
|
|
| etc. | |
|
|
|
|
|
9 |