Configuration Settings

 

 

 

 

Function

Factory Default

User Selectable

Description

Choices

 

 

 

 

 

 

 

 

Low Battery

2 minutes

• 2 m

• 14 m

PowerChute software interface provides auto-

Warning

 

• 5 m

• 17 m

matic, unattended shutdown when approxi-

 

 

• 8 m

• 20 m

mately two minutes of battery operated run

 

 

time remains.

 

 

• 11 m

• 23 m

 

 

The low-battery warning beeps are continuous

 

 

 

 

 

 

 

 

when two minutes of run time remain.

 

 

 

 

Change the low battery warning interval set-

 

 

 

 

ting to the time that the operating system or

 

 

 

 

system software requires to safely shut down.

 

 

 

 

 

Synchronized

0 seconds

• 0 s

• 240 s

Specify the time the UPS will wait after the

Turn-on Delay

 

• 60 s

• 300 s

return of utility power before start up (to avoid

 

 

• 120 s

• 360 s

branch circuit overload).

 

 

• 180 s

• 420 s

 

 

 

 

 

 

High Bypass Points

100V Models:

100V

120V

Maximum voltage that the UPS will pass to

 

110V

• 107V

• 127V

connected equipment during internal bypass

 

120V Models:

• 110V

• 130V

operation.

 

133V

• 113V

• 133V

 

 

 

• 116V

• 136V

 

 

 

• 119V

• 139V

 

 

 

• 122V

• 142V

 

 

 

• 125V

• 145V

 

 

 

• 128V

• 148V

 

 

 

 

 

 

Low Bypass Points

100V Models:

100V

120V

Minimum voltage that the UPS will pass to

 

78V

• 78V

• 86V

connected equipment during internal bypass

 

120V Models:

• 80V

• 88V

operation.

 

86V

• 82V

• 90V

 

 

 

• 84V

• 92V

 

 

 

• 86V

• 94V

 

 

 

• 88V

• 96V

 

 

 

• 90V

• 98V

 

 

 

• 92V

• 100V

 

 

 

 

 

 

Output Frequency

Automatic

50 ± 3 Hz or

 

Sets the allowable UPS output frequency.

 

50 ± 3 Hz or

50 ± 0.1 Hz

 

Whenever possible, the output frequency

 

60 ± 3 Hz

60 ± 3 Hz or

 

tracks the input frequency.

 

 

 

 

 

60 ± 0.1 Hz

 

 

 

 

 

 

Number of Battery

1

Number of connected bat-

Defines the number of connected battery packs

Packs

 

tery packs

 

for proper run time prediction.

 

 

 

 

1 = internal battery module,

 

 

 

 

2 = one SURTA48XLBP or SURTA48XLBPJ,

 

 

 

 

3 = two SURTA48XLBP or SURTA48XLBPJ,

 

 

 

 

etc.

 

 

 

 

 

Smart-UPS RT SURTA1500XL/SURTA1500XLJ/SURTA2000XL Uninterruptible Power Supply User Manual

9

Image 9
Contents Contact Information Safety Information Introduction/Before InstallationUnpacking and Equipment Placement About this ManualTo Install the UPS in a Rack InstallationTo Install the UPS as a Tower Configuration To Install the UPS with External Battery PacksIf Required, Connect the Emergency Power Off EPO Feature Connectors Type Description  Connect the Battery and Install the Front Bezel Terminal Mode Configuration Connect Power and Start Up the UPSFor Additional Computer System Security Display Panel Indicators OperationDisplay Panel LED On Battery OperationUtility Voltage Measurement Configuration SettingsFunction Factory Default User Selectable Description Choices To Install a Replacement Battery Storage, Maintenance, Transport, and ServiceStorage Transporting the UPS to Another LocationService Battery Replacement InstructionsProblem and/or Possible Cause Solution TroubleshootingEquipment There is no utility power Regulatory Approvals Radio Frequency WarningLimited Warranty Copyright Notice990-1856A 06/2004