APC configurationmanual Specifications, NetBotz Rack Monitor 200 NBRK0200

Page 27

Specifications

NetBotz Rack Monitor 200 (NBRK0200)

Electrical

Input voltage, nominal, for AC Line Inlet

100–240 Vac; 50/60 Hz

Maximum total current draw for AC Line Inlet

10 A (defined by Switched Outlet load + 0.25 A)

 

 

Maximum output voltage for Switched Outlet

Defined by input voltage

Maximum output current for Switched Outlet

10 A (defined by Switched Outlet load)

 

 

Voltage for Voltage Output contacts

12 Vdc, 24 Vdc

Current for Voltage Output contacts

75 mA total for 12 V or 24 V load

 

 

Current capacity of Relay Output contacts

1 A, 30 V AC/DC (rated for Class 2 circuits only)

 

 

Physical

 

 

 

Dimensions (H x W x D)

44.2 x 432.0 x 44.2 mm (1.74 x 17.00 x 1.74 in)

Shipping dimensions (H x W x D)

67 x 450 x 225 mm (2.6 x 17.8 x 8.9 in)

 

 

Weight

1.10 kg (2.50 lb)

Shipping weight

2.70 kg (6.00 lb)

Environmental

 

 

 

Elevation (above MSL)

 

Operating

0 to 3000 m (0 to 10,000 ft)

Storage

0 to 15 000 m (0 to 50,000 ft)

Temperature

 

Operating

0 to 45ºC (32 to 113°F)

Storage

–15 to 65°C (5 to 149°F)

Humidity

 

Operating

0 to 95%, non-condensing

Storage

0 to 95%, non-condensing

 

 

Performance

 

 

 

Typical Rack Monitor 200 response time for dry

200 mS

contact sensor or door switch sensor state changes

 

 

 

Compliance

 

 

 

Approvals

CE, C-UL tested to CSA C22.2 No. 60950-1-3, UL

 

60950-1, FCC Part 15 Class A, ICES-003 Class A,

 

VCCI Class A, EN 55022 Class A, EN 55024,

 

EN 61000-3-2, EN 61000-3-3, AS/NZS CISPR 22,

 

VDE tested to EN 60950–1

 

 

NetBotz Rack Monitor 200 Installation and Quick Configuration Manual

23

Image 27
Contents Installation Quick Configuration Manual Manual em Português está disponível no CD-ROM em anexo Contents Access the Rack Monitor Additional Documentation IntroductionProduct Description Document OverviewInventory Receiving InspectionInfraStruXure-certified Additional OptionsFront InstallationPhysical Description RearDescription Toolless peg-mount installation How to Install the Rack MonitorRack-mount installation Power cord and network cable connections How to Install the Temperature/Humidity Sensor How to Connect Sensors to Universal Sensor Ports How to Connect an Alarm Beacon and Other Optional Devices How to Cascade Devices to A-Link Ports How to Wire to the Modbus Interface Server type Procedure Quick ConfigurationHow to set up option How to disable the cookie requirementDhcp Server How to Update the Bootptab File Important Information about the Default GatewayHow to Use the APC Device IP Configuration Wizard Use apc for both User Name and Password How to Use ARP, Ping, and TelnetControl Console How to access the control consoleAccess the Rack Monitor Web InterfaceTelnet and SSH Simple Network Management Protocol Snmp Modbus How to Recover from a Lost PasswordNetBotz Rack Monitor 200 NBRK0200 SpecificationsSystem Specifications Temperature/Humidity Sensor AP9335THNon-transferable warranty Exclusions Warranty and Life SupportTwo-Year Factory Warranty Terms of warrantyWarranty claims Obtaining service Life Support Policy General policyExamples of life-support devices Page Page Page Taiwan-BSMI Radio Frequency InterferenceCanada-ICES Japan-VCCI2008 990-3283-001