APC NBRK0200 configurationmanual Temperature/Humidity Sensor AP9335TH, System Specifications

Page 28

Temperature/Humidity Sensor (AP9335TH)

Specifications

Temperature accuracy

±2ºC (±3ºF), from 0 to 40ºC (32 to 104ºF)

Humidity accuracy

±4% RH, 20 to 90%

RH, at 25ºC (77ºF)

 

±8% RH, 30 to 80%

RH, from 15 to 30ºC

 

(59 to 95ºF)

 

Sensor operating temperature

–10 to 70ºC (14 to 159ºF)

Cable length

4 m (13 ft)

 

 

 

 

System Specifications

A-Link

Maximum combined length of all A-Link

1000 m (3,280 ft)

cables

 

 

 

Maximum number of NetBotz Rack

12

Sensor Pod 150s that can be cascaded on

 

the A-Link bus

 

Maximum number of sensors (sensors

8

with digital display [AP9520T] and

 

Temperature/Humidity Sensors with

 

Digital Display [AP9520TH]) that can be cascaded on the A-Link bus

Temperature/Humidity Sensor (AP9335TH), Temperature Sensor (AP9335T),

Maximum length of cable

15 m (50 ft)

 

 

Beacon

 

 

 

Maximum length of cable

100 m (330 ft)

NetBotz Dry Contact Cable (NBES0304),

NetBotz 3.65-m (12-ft) Door Switch Sensor for APC Racks (NBES0303),

NetBotz 15.24-m (50-ft) Door Switch Sensor for Rooms or Third Party Racks (NBES0302)

Maximum length of cable

30.48 m (100 ft)

If a combined total of ten or more devices (NetBotz Rack Sensor Pod 150s [NBPD0150], Temperature Sensors with Digital Display [AP9520T], and Temperature/Humidity Sensors with Digital Display [AP9520TH]) are cascaded on the A-Link bus, a supplemental power supply (Power Supply 100-120 Vac/24 VdcAP9505i) is required. The power supply connects to the 24 VDC Input on a NetBotz Rack Sensor Pod 150.

24

NetBotz Rack Monitor 200 Installation and Quick Configuration Manual

Image 28
Contents Installation Quick Configuration Manual Manual em Português está disponível no CD-ROM em anexo Contents Access the Rack Monitor Introduction Product DescriptionDocument Overview Additional DocumentationReceiving Inspection InventoryAdditional Options InfraStruXure-certifiedInstallation Physical DescriptionRear FrontDescription How to Install the Rack Monitor Toolless peg-mount installationRack-mount installation Power cord and network cable connections How to Install the Temperature/Humidity Sensor How to Connect Sensors to Universal Sensor Ports How to Connect an Alarm Beacon and Other Optional Devices How to Cascade Devices to A-Link Ports How to Wire to the Modbus Interface Quick Configuration Server type ProcedureHow to disable the cookie requirement How to set up optionDhcp Server Important Information about the Default Gateway How to Update the Bootptab FileHow to Use the APC Device IP Configuration Wizard How to Use ARP, Ping, and Telnet Use apc for both User Name and PasswordHow to access the control console Control ConsoleWeb Interface Access the Rack MonitorTelnet and SSH Simple Network Management Protocol Snmp How to Recover from a Lost Password ModbusSpecifications NetBotz Rack Monitor 200 NBRK0200Temperature/Humidity Sensor AP9335TH System SpecificationsWarranty and Life Support Two-Year Factory WarrantyTerms of warranty Non-transferable warranty ExclusionsWarranty claims Obtaining service General policy Life Support PolicyExamples of life-support devices Page Page Page Radio Frequency Interference Canada-ICESJapan-VCCI Taiwan-BSMI990-3283-001 2008