American Power Conversion 240-320kW 480V manual System OFF Normal operation Load power 0%

Page 11

Stop/Start UPS and Operating the External Service Bypass

Action

1.Set the input switch (Q001) to position 1. If the system is energized by dual utility,

set the bypass input switch (Q010) to position "1".

2.Wait 5 sec. Open the front door of the UPS and press the green ON key

3.Press on the keyboard

Display shows

**System OFF**

Normal operation

load power 0%

4.

Press

or

on the keyboard until

Bypass operation

: NO

 

 

 

 

5.

Press

on the keyboard

Bypass operation

: YES

 

 

 

 

6.

Press

on the keyboard

Lamp indication on

 

 

 

 

 

 

 

 

Bypass Panel

7.

Check light indication on the bypass panel

Green light (H002)

 

 

 

 

above the output switch

 

 

 

 

handle (Q002) lights up

8.

Set the output switch (Q002) to position 1

Green light (H003)

 

 

 

 

above the bypass switch

 

 

 

 

handle (Q003) lights up

9.Set the bypass switch (Q003) to position 0

10.Press on the keyboard

11.Press or on the keyboard until

12. Press

on the keyboard

13.Press on the keyboard

14.Press on the keyboard

15. Press

on the keyboard

Only the light (H003) above the bypass switch handle (Q003) is now on

Display shows

Bypass operation

: YES

Bypass operation

: NO

Normal operation

load power 0%

All lights on the bypass panel switched off

NOTICE!

If battery has been disconnected, please refer to section 2.4.1 UPS start-up.

 

990-4039

 

 

User Guide APC Silcon 240-320kW 480V UPS

11

Image 11
Contents Copyright 2000 APC Denmark ApS APC Silcon 240-320kW 480V UPS User GuideThank You Safety Symbols used in this manualUser Guide APC Silcon 240-320kW 480V UPS Contents Display Unit IntroductionIntroduction Start UPS from stand-by Stop/Start UPS and Operating the External Service BypassStop UPS for stand-by Reset the acoustic alarm by pressing Stop UPS for complete power downSwitching off the UPS Acoustic alarm soundsUPS Start-up Start UPS from complete power downClose the front doors Operating the External Service Bypass Switch single systems Service Bypass Switch APC Silcon System OFF Normal operation Load power 0% Dual Utility Bypassing the Parallel UPS System All UPSsLamp indication on Bypass Panel Stop/Start UPS and Operating the External Service Bypass Following can be carried out on any UPS Press On the keyboardIsolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Keyboard OperationOperation Batt. load Batt. tank Display of Measured ValuesEconomy Mode Using the Remote DisplayParameter Setting Comments Parameter SettingsParameter Settings Parameter SettingsProgramming Example Switching to Bypass OperationProgramming Keys Load power xx% Displaying the Event Stack Alarms and EventsAlarms and Events Displaying the Alarm StackAlarms Description Action Possible alarmsDisplay will show invalid UPS data Correction of false alarm situations during service Rectifying Alarm MessagesParallel Operation Alarms Battery Capacity Test Maintenance & TestingMaintenance & Testing Battery Monitoring TestUntil APC Silcon UPS Limited Factory Warranty WarrantyWarranty APC Denmark How to Contact APCHow to Contact APC APC Corporate