Stop/Start UPS and Operating the External Service Bypass
The UPS is now isolated. Maintenance/repair, disconnection or removal can now be carried out.
CAUTION!
Recharge batteries out of service every 3 months to prevent damage.
WARNING!
Internal DC capacitor may contain energy even after the UPS has been switched off. Allow for automatic discharge by waiting at least 5 minutes after switching off UPS and battery breakers before working on the UPS.
2.4Start UPS (from complete power down)
2.4.1 UPS Start-up
CAUTION!
Make sure all cable connections are in place prior to first
NOTICE!
Green / ON
Red / OFF
After first system
NOTICE!
If for any reason the
CAUTION!
Do not close the MCCBs in the Battery Breaker Box unless the display reads: “Close MCCB” - otherwise the UPS may be damaged. If the display reads “DC capacitor charge error”, do not close MCCB.
Call for assistance.
| |
|
|
User Guide APC Silcon | 7 |