American Power Conversion 240-320kW 480V manual

Page 9

Stop/Start UPS and Operating the External Service Bypass

2.5Operating the External Service Bypass Switch (single systems)

2.5.1 Bypassing the Single System UPS

 

Single Utility

 

Utility

Load

Utility 2

 

Service Bypass

 

 

Switch

 

 

APC Silcon

Utility 1

 

UPS

 

 

Dual Utility

Load

Service Bypass

Switch

APC Silcon

UPS

Action

 

 

Display shows

1.

Press

on the keyboard

 

2.

Press

or

on the keyboard until

Bypass operation

: NO

 

 

 

 

3.

Press

on the keyboard

Bypass operation

: YES

 

 

 

 

4.

Press

on the keyboard

 

 

 

 

 

Lamp indication on

 

 

 

 

Bypass Panel

5.Check light indication on the bypass panel

6.Set the external bypass switch (Q003) to position 1

7.Set the output switch (Q002) to position 0

8.Open the front door and press the red OFF button.

The acoustic alarm sounds for 30 seconds*

9.Set the input switch (Q001) to position 0.

Set the bypass input switch (Q010) to position 0 (dual utility).

The red alarm LED below the display lights up and the acoustic alarm sounds for 30 seconds*

*Use the key to reset the acoustic alarm

Green light (H003) above the bypass switch handle (Q003) lights up

Green light (H002) above the output switch handle (Q002) lights up

Only the light (H002) above the output switch handle (Q002) is now on

Display shows

**System OFF**

 

990-4039

 

 

User Guide APC Silcon 240-320kW 480V UPS

9

Image 9
Contents Copyright 2000 APC Denmark ApS APC Silcon 240-320kW 480V UPS User GuideSafety Symbols used in this manual User Guide APC Silcon 240-320kW 480V UPSThank You Contents Introduction IntroductionDisplay Unit Stop/Start UPS and Operating the External Service Bypass Stop UPS for stand-byStart UPS from stand-by Switching off the UPS Stop UPS for complete power downAcoustic alarm sounds Reset the acoustic alarm by pressingUPS Start-up Start UPS from complete power downClose the front doors Operating the External Service Bypass Switch single systems Service Bypass Switch APC Silcon System OFF Normal operation Load power 0% Dual Utility Bypassing the Parallel UPS System All UPSsLamp indication on Bypass Panel Stop/Start UPS and Operating the External Service Bypass Following can be carried out on any UPS Press On the keyboardIsolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Batt. load Batt. tank Display of Measured ValuesEconomy Mode Using the Remote DisplayParameter Settings Parameter SettingsParameter Settings Parameter Setting CommentsSwitching to Bypass Operation Programming KeysProgramming Example Load power xx% Alarms and Events Alarms and EventsDisplaying the Alarm Stack Displaying the Event StackAlarms Description Action Possible alarmsDisplay will show invalid UPS data Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil Warranty WarrantyAPC Silcon UPS Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC Denmark