American Power Conversion 240-320kW 480V manual Close the front doors

Page 8

Stop/Start UPS and Operating the External Service Bypass

WARNING!

If “Autostart” is active the UPS will start automatically after step 9 (with a 1-minute delay).

1.Check that the system has been in a stable environment for at least 12 hours enabling any condensation to evaporate prior to start-up.

2.Open front door(s)

3.Switch on utility power by closing Q001 and Q010, if dual utility

4.Wait for approx. 10 seconds

5.Press on the keyboard

6.Press on the keyboard

7.Wait for approx. 1 second

8.Wait for approx. 1 minute

9.Close MCCBs in battery breaker Box or Battery Cabinet

10.Press the green ON button

Display shows

System type XXX

XXX kVA - XXX

Stop charge DC capacitors : YES

Start charge DC capacitors : YES

Data stored

Start charge DC capacitors : YES

Insert fuse or close MCCB

**System OFF**

Normal operation load power XX%

11. Close the front door(s)

System start-up now completed.

NOTICE!

One of the following display messages will appear by UPS start-up:

“STD”: Standard (single system)

“PAR”: Parallel System

“ECO”: Economy mode (single or parallel systems) (Last message has priority over the other two)

kVA size (XXX) and the voltage reads:

• XXXkVA - 208 (220 or 480 Volt)

 

990-4039

 

 

8

User Guide APC Silcon 240-320kW 480V UPS

Image 8
Contents APC Silcon 240-320kW 480V UPS User Guide Copyright 2000 APC Denmark ApSThank You Safety Symbols used in this manualUser Guide APC Silcon 240-320kW 480V UPS Contents Display Unit IntroductionIntroduction Start UPS from stand-by Stop/Start UPS and Operating the External Service BypassStop UPS for stand-by Stop UPS for complete power down Switching off the UPSAcoustic alarm sounds Reset the acoustic alarm by pressingStart UPS from complete power down UPS Start-upClose the front doors Operating the External Service Bypass Switch single systems Service Bypass Switch APC Silcon System OFF Normal operation Load power 0% Bypassing the Parallel UPS System All UPSs Dual UtilityLamp indication on Bypass Panel Stop/Start UPS and Operating the External Service Bypass Press On the keyboard Following can be carried out on any UPSIsolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Keyboard OperationOperation Display of Measured Values Batt. load Batt. tankUsing the Remote Display Economy ModeParameter Settings Parameter SettingsParameter Settings Parameter Setting CommentsProgramming Example Switching to Bypass OperationProgramming Keys Load power xx% Alarms and Events Alarms and EventsDisplaying the Alarm Stack Displaying the Event StackPossible alarms Alarms Description ActionDisplay will show invalid UPS data Correction of false alarm situations during service Rectifying Alarm MessagesParallel Operation Alarms Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil APC Silcon UPS Limited Factory Warranty WarrantyWarranty How to Contact APC How to Contact APCAPC Corporate APC Denmark