American Power Conversion 240-320kW 480V manual Lamp indication on Bypass Panel

Page 13

Stop/Start UPS and Operating the External Service Bypass

Action

Steps 1-4 apply to all the parallel systems. Note that this will switch all systems into bypass operation

1.

Press

on the keyboard

Display shows

 

2.

Press

or

on the keyboard until

Bypass operation

 

 

 

 

: NO

3.

Press

on the keyboard

Bypass operation

 

 

 

 

: YES

4.

Press

on the keyboard

 

All systems switch to bypass operation

Do not switch off any of the UPS systems until steps 5-8 have been completed

5.Check light indication on the bypass panel

6.Set the external bypass switch (Q003) to position 1

7.Set the output switch (Q004) to position 0

8.Set all output switches (Q002) to position 0

9.Open the front door of any one system and press the red OFF button

The acoustic alarm sounds for 30 secs* Repeat for (all) other system(s)

10.Set all input switches (Q001) to position 0 Set bypass input switches

(Q010) to position 0 (dual utility)

The red alarm LED below the display lights up and the acoustic alarm sounds for 30 secs*

Bypass operation

Lamp indication on Bypass Panel

Green light (H003) above the bypass switch handle (Q003) lights up

Green light (H004) above the output switch handle (Q004) and green lights (H002) above the output switch handles (Q002) light up

H003 switches off

H002 and H004 still on

H002 and H004 still on

Display shows

**System OFF**

*Reset the acoustic alarm by pressing the key.

 

990-4039

 

 

User Guide APC Silcon 240-320kW 480V UPS

13

Image 13
Contents Copyright 2000 APC Denmark ApS APC Silcon 240-320kW 480V UPS User GuideUser Guide APC Silcon 240-320kW 480V UPS Safety Symbols used in this manualThank You Contents Introduction IntroductionDisplay Unit Stop UPS for stand-by Stop/Start UPS and Operating the External Service BypassStart UPS from stand-by Switching off the UPS Stop UPS for complete power downAcoustic alarm sounds Reset the acoustic alarm by pressingUPS Start-up Start UPS from complete power downClose the front doors Operating the External Service Bypass Switch single systems Service Bypass Switch APC Silcon System OFF Normal operation Load power 0% Dual Utility Bypassing the Parallel UPS System All UPSsLamp indication on Bypass Panel Stop/Start UPS and Operating the External Service Bypass Following can be carried out on any UPS Press On the keyboardIsolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Batt. load Batt. tank Display of Measured ValuesEconomy Mode Using the Remote DisplayParameter Settings Parameter SettingsParameter Settings Parameter Setting CommentsProgramming Keys Switching to Bypass OperationProgramming Example Load power xx% Alarms and Events Alarms and EventsDisplaying the Alarm Stack Displaying the Event StackAlarms Description Action Possible alarmsDisplay will show invalid UPS data Parallel Operation Alarms Rectifying Alarm MessagesCorrection of false alarm situations during service Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil Warranty WarrantyAPC Silcon UPS Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC Denmark