American Power Conversion 240-320kW 480V Stop UPS for complete power down, Switching off the UPS

Page 6

Stop/Start UPS and Operating the External Service Bypass

2.3Stop UPS (for complete power down)

2.3.1 Switching off the UPS

CAUTION!

If the UPS system is equipped with a Service Bypass Panel, and if the load must remain energized by utility, refer to the Operating Service Bypass Panel sections in this guide before proceeding

Green / ON

Red / OFF

WARNING!

TEST BEFORE YOU TOUCH!

A special design feature switches the system into bypass operation in the event of internal power supply failure or controller circuit failure to ensure uninterrupted output voltage.

Because of this special feature, the UPS may contain output voltage even when it is switched off.

1.Open front doors

2.Note that step 3 will interrupt output voltage and activate the alarm! The red LED alarm below the display will light up

The acoustic alarm will sound for 30 seconds*

3.Press the red OFF button.

The red LED alarm below the display will light up The acoustic alarm will sound for 30 seconds*

4.On systems with no Service Bypass Panel, switch off the utility supply

5.The red LED alarm below the display will light up The acoustic alarm will sound for 30 seconds

6.Switch off battery breakers F001 and F002 in the Battery Breaker Box or battery cabinet

Refer to LED indication and labelling in Battery Breaker Box or battery cabinet

7.To switch off utility supply, open Q001 – on systems with Service Bypass Panel.

Display shows

**System OFF**

**System OFF**

 

8. The acoustic alarm sounds

Blank

 

*Reset the acoustic alarm by pressing .

 

 

 

990-4039

6

User Guide APC Silcon 240-320kW 480V UPS

Image 6
Contents APC Silcon 240-320kW 480V UPS User Guide Copyright 2000 APC Denmark ApSSafety Symbols used in this manual User Guide APC Silcon 240-320kW 480V UPSThank You Contents Introduction IntroductionDisplay Unit Stop/Start UPS and Operating the External Service Bypass Stop UPS for stand-byStart UPS from stand-by Acoustic alarm sounds Stop UPS for complete power downSwitching off the UPS Reset the acoustic alarm by pressingStart UPS from complete power down UPS Start-upClose the front doors Operating the External Service Bypass Switch single systems Service Bypass Switch APC Silcon System OFF Normal operation Load power 0% Bypassing the Parallel UPS System All UPSs Dual UtilityLamp indication on Bypass Panel Stop/Start UPS and Operating the External Service Bypass Press On the keyboard Following can be carried out on any UPSIsolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Display of Measured Values Batt. load Batt. tankUsing the Remote Display Economy ModeParameter Settings Parameter SettingsParameter Settings Parameter Setting CommentsSwitching to Bypass Operation Programming KeysProgramming Example Load power xx% Displaying the Alarm Stack Alarms and EventsAlarms and Events Displaying the Event StackPossible alarms Alarms Description ActionDisplay will show invalid UPS data Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Battery Monitoring Test Maintenance & TestingMaintenance & Testing Battery Capacity TestUntil Warranty WarrantyAPC Silcon UPS Limited Factory Warranty APC Corporate How to Contact APCHow to Contact APC APC Denmark