APC Switched Rack Power Distribution Unit (PDU) manual Upgrading Firmware, Xmodem

Page 10

USER’S GUIDE switched rack pdu

®

Upgrading Firmware

0

For a complete description of how to download a firmware upgrade for your PDU, see the Management Card Addendum (.\doc\Addendum.pdf) on the provided APC PDU Utility CD.

You can use a local computer that connects to the PDU through the serial port on the front panel of the unit.

1.Select a serial port at the local computer, and disable any service which uses that port.

2.Use the supplied serial cable (940-0144) to connect the selected port to the RJ-12 serial port on the front panel of the PDU.

3.Run a terminal program (such as HyperTerminal) and configure the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control. Save the changes.

4.Press ENTER twice to display the User Name prompt.

5.Enter your user name and password (both apc, for administrators only) and press the ENTER key.

6.From the Control Console menu, select System, then Tools, then

XMODEM.

7.At the prompt Perform transfer with XMODEM-CRC?type YES, and press ENTER.

8.The system will then prompt you to choose a transfer rate and to change your terminal settings to match the transfer rate. Press ENTER to set the Switched Rack PDU to accept the download.

6

Image 10
Contents Contents Web Interface Network Menu Index Introduction Features of the PDUProduct Description Initial setup Access priority for logging on Access ProceduresOverview Types of user accounts How to Recover From a Lost Password Upgrading Firmware XmodemUSER’S Guide switched rack pdu Three-phase Single-phaseFront Panel See Status LED Status LED Link-RX/TX 10/100 LEDCondition Description Load indicator LED Resetting the network timer Watchdog FeaturesNetwork interface watchdog mechanism Remote access to the control console How to Log OnControl Console Local access to the control console Example main screen Main ScreenInformation and status fields System Menu Main screen status fields Control Console Menus Menu structureDevice Manager option Main menuNetwork option System option Web Interface Supported Web browsers URL address formats Summary StatusQuick status tab Navigation menuNavigation Menu Events menu Network menu System menuSelecting a menu to perform a task Help menu Links menu Device Manager Menus Outlet SettingsPower On Delays Control outletsConfigure outlet settings and outlet name For Power Off DelaySelect Outlet Control/Config from the Device Manager menu Setting DescriptionSwitched Rack PDU Settings Configure Load ThresholdsUSER’S Guide switched rack pdu Configure Device Settings Control consoleEvent-Related Menus IntroductionMenu options Event Log Logged events Web interfaceControl console How to use FTP to retrieve log files USER’S Guide switched rack pdu Event Actions Web Interface Only Event log action Severity levelsSnmp traps action Email action Event Recipients Trap receiver settingsDefinition Mail Feature Smtp settings DNS serversEmail Recipients USER’S Guide switched rack pdu Event List How to Configure Individual EventsDetailed Event Action Configuration Code Description SeveritySystem Menu Menu options Administrator and Device Manager User Option SettingsSetting Definition User ManagerOutlet Manager Identification Date & TimeUSER’S Guide switched rack pdu Tools Action DefinitionLinks Web interface APC’s Web Site , Testdrive Demo , and Remote MonitoringAbout System Network Menu TCP/IP DNSTCP/IP For more information on using Bootp and DHCP, see Boot Mode DNS Ping utility control console FTP Server, and Telnet & Web options Ftp Telnet Http//159.215.12.11432740Snmp USER’S Guide switched rack pdu Boot Mode Dhcp & Bootp boot process See Switched Rack PDU settingsDhcp Configuration Settings Switched Rack PDU settingsUSER’S Guide switched rack pdu Dhcp response options APC Cookie. Tag 1, Len 4, Data 1APCBoot Mode Transition. Tag 2, Len 1, Data 1/2 USER’S Guide switched rack pdu User names, passwords, community names Security FeaturesPlanning and implementing security features SecuritySummary of access methods Interface Security AccessAuthentication versus encryption AuthenticationFirewalls USER’S Guide Limited warranty Warranty and ServiceProduct Information Warranty limitations Obtaining serviceUSER’S Guide switched rack pdu General policy Life-Support PolicyExamples of life-support devices Index APC OSFTP Smtp Xmodem APC Worldwide Customer Support Copyright