American Power Conversion 5000VA user manual Brightly

Page 17

Function

Factory

User Selectable

 

Description

Default

Choices

 

 

 

 

 

 

Low Battery

2 minutes

Brightly

 

The low-battery warning beeps are continuous

Warning

 

illuminated:

when two minutes of run time remain.

PowerChute

LED is located

low battery warning

To change the default interval setting, use a

software interface

level of about 2 minutes

pointed object such as a pen to press the

on rear panel

provides automatic,

Dimly illuminated:

VOLTAGE SENSITIVIY switch (rear panel),

 

unattended

 

while

 

 

low battery

 

shutdown when

 

 

 

 

warning level of about

 

 

approximately two

 

pressing the

button, (front display).

 

5 minutes

 

minutes of battery

 

 

 

No illumination:

Change the low battery warning interval setting

operated run time

 

remains.

 

low battery warning

to the time that the operating system or system

 

software requires to safely shut down.

 

 

level is about 8 minutes

 

 

 

 

 

 

 

 

 

Synchronized

0 seconds

• 0 s

• 240 s

Specify the time the UPS will wait after the

Turn-on Delay

 

• 60 s

• 300 s

return of utility power before start up, (to avoid

 

 

• 120 s

• 360 s

branch circuit overload).

 

 

• 180 s

• 420 s

 

 

 

 

 

 

 

High Transfer Point

208 V models:

 

 

To avoid unnecessary use of the battery where

 

225 Vac

• 225 Vac

• 233 Vac

utility voltage is chronically high, set the high

 

 

• 229 Vac

237 Vac

transfer point higher if the connected

 

230 V models:

equipment can tolerate this condition.

 

 

 

 

 

 

 

 

 

253 Vac

• 253 Vac

• 261 Vac

 

 

 

 

• 257 Vac

• 265 Vac

 

 

 

 

 

 

 

Low Transfer Point

208 V models:

To avoid unnecessary use of the battery where

 

182 Vac

• 182 Vac

• 174 Vac

utility voltage is chronically low, set the low

 

 

• 178 Vac

• 170 Vac

transfer point lower if the connected equipment

 

 

can tolerate this condition.

 

230 V models:

 

 

 

 

 

 

 

 

208 Vac

• 196 Vac

• 204 Vac

 

 

 

 

• 200 Vac

• 208 Vac

 

 

 

 

 

 

 

Output Voltage

 

• 220 Vac

• 240 Vac

Set the output voltage of the UPS.

230 V models

230 Vac

 

 

 

 

• 230 Vac

 

 

 

 

 

 

 

 

 

Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual

13

Image 17
Contents APC Smart-UPS→ Page Contents Page Unpack Read the Safety Guide before installing the UPSAbout this UPS Installation SpecificationsRack-mount configuration Install rack-mount brackets and rail cleatsInstall unit in rack Install two top covers Rack-mount to tower conversion procedureInstall stabilizer brackets Connect the ground wire prior to connecting the line wires Input hardwire 230 V models onlyAccessories Connect batteries Configure bezelRack-mount configuration Tower configuration Rack-mount configuration Connect display cable and install bezelStart the UPS Connect Equipment and Power to the UPSRear Panels Communication Ports Emergency Power OffIndicator Indicator Title Description Display Panel Indicators and Function ButtonsDisplay Panels ModelsFeature Feature Title Function Button Function Factory User Selectable Description Default Choices UPS settingsBrightly Problem and/or Possible Cause Solution TroubleshootingReplace Battery/Battery Disconnected LED is illuminated There is no utility power Install new batteries Maintenance, Transport, and ServiceReplace battery modules Service Terms of warranty Two-Year WarrantyFCC Compliance Notice Models Regulatory InformationDate of product declaration