American Power Conversion 5000VA user manual UPS settings

Page 16

Configuration

UPS settings

Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.

Function

Factory

User Selectable

Description

Default

Choices

 

 

 

 

Automatic

On startup and

• On startup and every

Set the interval at which the UPS will execute a

Self-Test

every 14 days

7 days (168 hours)

self-test.

 

(336 hours)

there after

 

 

 

there after

• On startup and every

 

 

 

14 days (336 hours)

 

 

 

there after

 

 

 

 

• On startup only

 

 

 

• No self-test

 

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters

Uniquely identify the UPS, (i.e. server name or

 

 

(alphanumeric)

location) for network management purposes.

 

 

 

 

 

Date of Last

Manufacture

mm/dd/yy

 

Reset this date when you replace the battery

Battery

Date

 

 

module.

Replacement

 

 

 

 

 

 

 

 

 

Minimum Capacity

0 percent

• 0%

• 60%

Specify the percentage to which batteries will

Before Return from

 

• 15%

• 75%

be charged following a low battery shutdown

Shutdown

 

• 30%

• 90%

before powering connected equipment.

 

 

• 45%

 

 

 

 

 

 

 

Voltage Sensitivity

High sensitivity

Brightly

 

Adjust by pressing the VOLTAGE SENSITIVIY

The UPS detects

 

illuminated: high

switch (rear panel). Use a pointed object, (such

 

sensitivity

as a pen) to do so.

and reacts to line

 

voltage distortions

 

Dimly illuminated:

Note: In situations of poor power quality, the

by transferring to

 

medium sensitivity

UPS may frequently transfer to battery

battery operation to

 

No illumination:

operation. If the connected equipment can

protect the

 

operate normally under such conditions, reduce

 

low sensitivity

connected

 

the sensitivity setting to conserve battery

 

 

 

equipment.

 

 

 

capacity and service life.

 

 

 

 

 

Alarm Delay

Enable

• Enable

 

Mute ongoing alarms or disable all alarms.

Control

 

• Mute

 

 

 

 

• Disable

 

 

 

 

 

 

 

Shutdown Delay

90 seconds

• 0 s

• 360 s

Set the interval between the time when the UPS

 

 

• 90 s

• 450 s

receives a shutdown command and actual

 

 

• 180 s

• 540 s

shutdown.

 

 

• 270 s

• 630 s

 

 

 

 

 

 

12

Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual

Image 16
Contents APC Smart-UPS→ Page Contents Page About this UPS Read the Safety Guide before installing the UPSUnpack Specifications InstallationRack-mount configuration Install rack-mount brackets and rail cleatsInstall unit in rack Install stabilizer brackets Rack-mount to tower conversion procedureInstall two top covers Accessories Input hardwire 230 V models onlyConnect the ground wire prior to connecting the line wires Rack-mount configuration Tower configuration Configure bezelConnect batteries Connect display cable and install bezel Rack-mount configurationRear Panels Connect Equipment and Power to the UPSStart the UPS Emergency Power Off Communication PortsDisplay Panel Indicators and Function Buttons Indicator Indicator Title DescriptionDisplay Panels ModelsFeature Feature Title Function Button UPS settings Function Factory User Selectable Description Default ChoicesBrightly Troubleshooting Problem and/or Possible Cause SolutionReplace Battery/Battery Disconnected LED is illuminated There is no utility power Replace battery modules Maintenance, Transport, and ServiceInstall new batteries Service Two-Year Warranty Terms of warrantyRegulatory Information FCC Compliance Notice ModelsDate of product declaration