APC SMX 1500 VA, SMX48RMBP2U, SMX750 VA, SMX1000 VA operation manual Controllable Outlet Groups

Page 10

Function

Factory Default

Options

Description

 

 

 

 

 

 

 

Select the level of sensitivity to power events that the UPS

 

 

 

will tolerate.

 

 

 

• High: The UPS will go on battery power more often to

Transfer

 

 

provide the cleanest power supply to the connected

High

High, Low, Medium

equipment.

Sensitivity

• Low: The UPS will tolerate more fluctuations in power

 

 

 

and will go on battery power less often.

 

 

 

If the connected load is sensitive to power disturbances, set

 

 

 

the sensitivity to High.

 

 

 

 

Low

 

 

The UPS will emit an audible alarm when the remaining

Battery

150 sec

Set the value in seconds

Warning

 

 

runtime has reached this level.

 

 

 

 

 

 

 

Date of

 

 

 

Last

 

 

 

Battery

Date set at factory

Reset this date when the battery module is replaced.

Replaceme

 

 

 

nt

 

 

 

 

 

 

 

Audible

On

On/Off

The UPS will mute all audible alarms if this is set to Off or

Alarm

when the display buttons are pressed.

 

 

 

 

 

 

Battery

 

• Never

 

Self-Test

On start up and every • Start up only

 

Interval

14 days since the last • Frequency of test (days) The interval at which the UPS will execute a self-test.

Setting

test

 

 

 

 

 

 

 

 

 

Reset to

 

 

 

Factory

No

Yes/No

Restore the UPS factory default settings.

Default

 

 

 

Controllable Outlet Groups

Overview

The rear panel of the UPS has multiple outlets, some are grouped into Controllable Outlet Groups, all of the other outlets are the UPS outlets, which function as an outlet group. All of these groups can independently turn off, turn on, shut down, and reboot connected equipment.

The Controllable Outlet Groups can be commanded to do the following:

Turn off: Disconnect from power immediately and restart only with a manual command

Turn on: Connect to power immediately

Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when utility power becomes available

Reboot: Shut down and restart

In addition, the Controllable Outlet Groups and the UPS outlets can be configured to do the following:

Turn on or off in a specified sequence

Automatically turn off or shut down when various conditions occur

Note: If the Controllable Outlet Groups are not configured, all of the outlets on the unit will still provide battery backup power.

8

Smart-UPS X 750/1000/1500 VA 120/230 Vac Rack-Mount 2U

Image 10
Contents Smart-UPS X Uninterruptible Power Supply Page Safety and General Information Important Safety MessagesProduct Description Product Overview Front Panel FeaturesRear Panel Features 120 VacEnvironmental Specifications SpecificationsInstallation Network Management Card External Battery PackOperation Basic ConnectorsConnect Equipment to the UPS Overview Using the display interfaceDisplay Panel Standard menusControl Advanced menusLog Start up settings ConfigurationUPS Settings General SettingsControllable Outlet Groups 1000 VA 120/230 Vac Model specific controllable outlet groups750 VA 120 Vac 1500 VA 120/230 VacUsing the controllable outlet groups and UPS outlets Reboot Duration Turn On DelayTurn Off Delay On BatteryNetwork Management Card Settings Normally open contacts Emergency Power OffNormally closed contacts UPS is emits intermittent beeps TroubleshootingUPS does not provide expected backup time Display interface LEDs flash sequentiallyReplace Battery LED is illuminated UPS displays a site wiring fault messageService Transport the unitTwo Year Limited Factory Warranty Non-transferable warrantyPage APC by Schneider Electric Worldwide Customer Support 990-3458B 04/2013